5 demand metering, 6 analog inputs, 7 speed – GE 489 User Manual

Page 149: Demand metering -17, Analog inputs -17, Speed -17

Advertising
background image

GE Multilin

489 Generator Management Relay

5-17

5 ACTUAL VALUES

5.3 A2 METERING DATA

5

5.3.5 DEMAND METERING

PATH: ACTUAL VALUES

ÖØ

A2 METERING DATA

ÖØ

DEMAND METERING

The values for current and power demand are shown here. This peak demand information can be cleared using the

S1 489

SETUP

ÖØ

CLEAR DATA

ÖØ

CLEAR PEAK DEMAND

setpoint. Demand is shown only for positive real and positive reactive

power (+Watts, +vars). Peak demand will not update if a digital input programmed as Test Input is shorted.

5.3.6 ANALOG INPUTS

PATH: ACTUAL VALUES

ÖØ

A2 METERING DATA

ÖØ

ANALOG INPUTS

The values for analog inputs are shown here. The name of the input and the units will reflect those programmed for each
input. If no analog inputs are programmed in the

S11 ANALOG I/O

setpoints page, the

THIS FEATURE NOT PROGRAMMED

flash message will appear when an attempt is made to enter this group of messages.

5.3.7 SPEED

PATH: ACTUAL VALUES

ÖØ

A2 METERING DATA

ÖØ

SPEED

If the Tachometer function is assigned to one of the digital inputs, its speed be viewed here. A bar graph on the second line
of this message represents speed from 0 RPM to rated speed. If no digital input is configured for tachometer, the

THIS FEA-

TURE NOT PROGRAMMED

flash message will appear when an attempt is made to enter this group of messages.

„ DEMAND METERING
„ [ENTER] for more

CURRENT

DEMAND: 0 Amps

Range: 0 to 999999 A

MW DEMAND:

0.000 MW

Range: 0.000 to 2000.000 MW. Not seen if VT

CONNECTION TYPE is programmed as None

Mvar DEMAND:

0.000 Mvar

Range: 0.000 to 2000.000 Mvar. Not seen if VT

CONNECTION TYPE is programmed as None

MVA DEMAND:

0.000 MVA

Range: 0.000 to 2000.000 MVA. Not seen if VT

CONNECTION TYPE is programmed as None

PEAK CURRENT

DEMAND: 0 Amps

Range: 0 to 999999 A

PEAK MW DEMAND:

0.000 MW

Range: 0.000 to 2000.000 MW. Not seen if VT

CONNECTION TYPE is programmed as None

PEAK Mvar DEMAND:

0.000 Mvar

Range: 0.000 to 2000.000 Mvar. Not seen if VT

CONNECTION TYPE is programmed as None

PEAK MVA DEMAND:

0.000 MVA

Range: 0.000 to 2000.000 MVA. Not seen if VT

CONNECTION TYPE is programmed as None

„ ANALOG INPUTS
„ [ENTER] for more

ANALOG I/P 1

0 Units

Range: –50000 to 50000. Message seen only if Analog

Input is programmed. Message reflects Analog
Input Name as programmed.

ANALOG I/P 2

0 Units

Range: as for ANALOG I/P 1 above

ANALOG I/P 3

0 Units

Range: as for ANALOG I/P 1 above

ANALOG I/P 4

0 Units

Range: as for ANALOG I/P 1 above

„ SPEED
„ [ENTER] for more

TACHOMETER: 0 RPM

Range: 0 to 7200 RPM. Seen only if a digital input is

configured as Tachometer.