GE 489 User Manual

Page 192

Advertising
background image

6-30

489 Generator Management Relay

GE Multilin

6.3 MODBUS MEMORY MAP

6 COMMUNICATIONS

6

2B37

VOLTS/HERTZ MAX

0 to 200

1

× Rated

F3

150

2B38

FREQUENCY MIN

0 to 9000

1

Hz

F3

5900

2B39

FREQUENCY MAX

0 to 9000

1

Hz

F3

6100

2B3C

POWER FACTOR MIN

–99 to 100

1

F6

80

2B3D

POWER FACTOR MAX

–99 to 100

1

F6

–80

2B3E

REACTIVE POWER MIN

–200 to 200

1

× Rated

F6

0

2B3F

REACTIVE POWER MAX

–200 to 200

1

× Rated

F6

125

2B40

REAL POWER (MW) MIN

–200 to 200

1

× Rated

F6

0

2B41

REAL POWER (MW) MAX

–200 to 200

1

× Rated

F6

125

2B42

APPARENT POWER MIN

0 to 200

1

× Rated

F3

0

2B43

APPARENT POWER MAX

0 to 200

1

× Rated

F3

125

2B44

ANALOG INPUT 1 MIN

–50000 to 50000

1

Units

F12

0

2B46

ANALOG INPUT 1 MAX

–50000 to 50000

1

Units

F12

50000

2B48

ANALOG INPUT 2 MIN

–50000 to 50000

1

Units

F12

0

2B4A

ANALOG INPUT 2 MAX

–50000 to 50000

1

Units

F12

50000

2B4C

ANALOG INPUT 3 MIN

–50000 to 50000

1

Units

F12

0

2B4E

ANALOG INPUT 3 MAX

–50000 to 50000

1

Units

F12

50000

2B50

ANALOG INPUT 4 MIN

–50000 to 50000

1

Units

F12

0

2B52

ANALOG INPUT 4 MAX

–50000 to 50000

1

Units

F12

50000

2B54

TACHOMETER MIN

0 to 7200

1

RPM

F1

3500

2B55

TACHOMETER MAX

0 to 7200

1

RPM

F1

3700

2B56

THERM. CAPACITY USED MIN

0 to 100

1

%

F1

0

2B57

THERM. CAPACITY USED MAX

0 to 100

1

%

F1

100

2B58

NEUTRAL VOLT THIRD MIN

0 to 250000

1

Volts

F10

0

2B5A

NEUTRAL VOLT THIRD MAX

0 to 250000

1

Volts

F10

450

2B5C

CURRENT DEMAND MIN

0 to 2000

1

× FLA

F3

0

2B5D

CURRENT DEMAND MAX

0 to 2000

1

× FLA

F3

125

2B5E

Mar DEMAND MIN

0 to 200

1

× Rated

F3

0

2B5F

Mar DEMAND MAX

0 to 200

1

× Rated

F3

125

2B60

MW DEMAND MIN

0 to 200

1

× Rated

F3

0

2B61

MW DEMAND MAX

0 to 200

1

× Rated

F3

125

2B62

MVA DEMAND MIN

0 to 200

1

× Rated

F3

0

2B63

MVA DEMAND MAX

0 to 200

1

× Rated

F3

125

ANALOG I/O / ANALOG INPUT 1

2C00

ANALOG INPUT1

0 to 3

1

F129

0

2C05

ANALOG INPUT1 UNITS

0 to 6

1

F22

_

2C08

ANALOG INPUT1 MINIMUM

–50000 to 50000

1

Units

F12

0

2C0A

ANALOG INPUT1 MAXIMUM

–50000 to 50000

1

Units

F12

100

2C0C

BLOCK ANALOG INPUT1 FROM ONLINE

0 to 5000

1

s

F1

0

2C0D

ANALOG INPUT1 ALARM

0 to 2

1

F115

0

2C0E

ASSIGN ALARM RELAYS (2-5)

1 to 4

1

F50

16

2C0F

ANALOG INPUT1 ALARM LEVEL

–50000 to 50000

1

Units

F12

10

2C11

ANALOG INPUT1 ALARM PICKUP

0 to 1

1

F130

0

2C12

ANALOG INPUT1 ALARM DELAY

1 to 3000

1

s

F2

1

2C13

ANALOG INPUT1 ALARM EVENTS

0 to 1

1

F105

0

2C14

ANALOG INPUT1 TRIP

0 to 2

1

F115

0

2C15

ASSIGN TRIP RELAYS (1-4)

0 to 3

1

F50

1

2C16

ANALOG INPUT1 TRIP LEVEL

–50000 to 50000

1

Units

F12

20

2C18

ANALOG INPUT1 TRIP PICKUP

0 to 1

1

F130

0

2C19

ANALOG INPUT1 TRIP DELAY

1 to 3000

1

s

F2

1

2C1A

ANALOG INPUT1 NAME

0 to 12

1

F22

_

ANALOG I/O / ANALOG INPUT 2

2C40

ANALOG INPUT2

0 to 3

1

F129

0

2C45

ANALOG INPUT2 UNITS

0 to 6

1

F22

_

2C48

ANALOG INPUT2 MINIMUM

–50000 to 50000

1

Units

F12

0

2C4A

ANALOG INPUT2 MAXIMUM

–50000 to 50000

1

Units

F12

100

2C4C

BLOCK ANALOG INPUT2 FROM ONLINE

0 to 5000

1

s

F1

0

2C4D

ANALOG INPUT2 ALARM

0 to 2

1

F115

0

2C4E

ASSIGN ALARM RELAYS (2-5)

1 to 4

1

F50

16

2C4F

ANALOG INPUT2 ALARM LEVEL

–50000 to 50000

1

Units

F12

10

2C51

ANALOG INPUT2 ALARM PICKUP

0 to 1

1

F130

0

2C52

ANALOG INPUT2 ALARM DELAY

1 to 3000

1

s

F2

1

2C53

ANALOG INPUT2 ALARM EVENTS

0 to 1

1

F105

0

2C54

ANALOG INPUT2 TRIP

0 to 2

1

F115

0

2C55

ASSIGN TRIP RELAYS (1-4)

0 to 3

1

F50

1

2C56

ANALOG INPUT2 TRIP LEVEL

–50000 to 50000

1

Units

F12

20

Table 6–1: 489 MEMORY MAP (SHEET 21 OF 24)