4-48

489 Generator Management Relay

GE Multilin

4.8 S7 POWER ELEMENTS

4 SETPOINTS

4

4.8.4 LOW FORWARD POWER

PATH: SETPOINTS

ÖØ

S7 POWER ELEMENTS

ÖØ

LOW FORWARD POWER

If enabled, once the magnitude of 3-phase total power in the forward direction (+MW) falls below the Pickup Level for a
period of time specified by the Delay, an alarm will occur. The level is programmed in per unit of generator rated MW calcu-
lated from the rated MVA and rated power factor. The low forward power element is active only when the generator is online
and will be blocked until the generator is brought online, for a period of time defined by the setpoint Block Low Fwd Power
From Online. The pickup level should be set lower than expected generator loading during normal operations. If the VT
type is selected as "None" or VT fuse loss is detected, the low forward power protection is disabled.

„ LOW FORWARD POWER
„ [ENTER] for more

BLOCK LOW FWD POWER

FROM ONLINE: 0 s

Range: 0 to 15000 s in steps of 1

LOW FORWARD POWER

ALARM: Off

Range: Off, Latched, Unlatched

ASSIGN ALARM

RELAYS (2-5): ---5

Range: Any combination of Relays 2 to 5

LOW FWD POWER ALARM

LEVEL: 0.05 x Rated MW

Range: 0.02 to 0.99

× Rated MW in steps of 0.01

LOW FWD POWER ALARM

DELAY: 10.0 s

Range: 0.2 to 120.0 s in steps of 0.1

LOW FWD POWER ALARM

EVENTS: Off

Range: On, Off

LOW FORWARD POWER

TRIP: Off

Range: Off, Latched, Unlatched

ASSIGN TRIP

RELAYS (1-4): 1---

Range: Any combination of Relays 1 to 4

LOW FWD POWER TRIP

LEVEL: 0.05 x Rated MW

Range: 0.02 to 0.99

× Rated MW in steps of 0.01

LOW FWD POWER TRIP

DELAY: 20.0 s

Range: 0.2 to 120.0 s in steps of 0.1

ENTER

ESCAPE

р

р

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE