489 Generator Management Relay

4-9

4 SETPOINTS

4.2 S1 489 SETUP

4

4.2.4 REAL TIME CLOCK

PATH: SETPOINTS

Ö

S1 489 SETUP

ÖØ

REAL TIME CLOCK

For events that are recorded by the event recorder to be correctly time/date stamped, the correct time and date must be
entered. A battery backed internal clock runs continuously even when power is off. It has the same accuracy as an elec-
tronic watch approximately ±1 minute per month. It must be periodically corrected either manually through the front panel or
via the clock update command over the RS485 serial link. If the approximate time an event occurred without synchroniza-
tion to other relays is sufficient, then entry of time/date from the front panel keys is adequate.

If the RS485 serial communication link is used then all the relays can keep time in synchronization with each other. A new
clock time is pre-loaded into the memory map via the RS485 communications port by a remote computer to each relay con-
nected on the communications channel. The computer broadcasts (address 0) a "set clock" command to all relays. Then all
relays in the system begin timing at the exact same instant. There can be up to 100 ms of delay in receiving serial com-
mands so the clock time in each relay is ±100 ms, ± the absolute clock accuracy in the PLC or PC. See the chapter on
Communications for information on programming the time preload and synchronizing commands.

An IRIG-B signal receiver may be connected to 489 units with hardware revision G or higher. The relay will continuously
decode the time signal and set its internal time correspondingly. The “signal type” setpoint must be set to match the signal
provided by the receiver.

4.2.5 DEFAULT MESSAGES

PATH: SETPOINTS

Ö

S1 489 SETUP

ÖØ

DEFAULT MESSAGES

„ REAL TIME CLOCK
„ [ENTER] for more

DATE (MM, DD, YYYY):

01/01/1995

Range: 01/01/1995 to 12/31/2094

TIME (HH.MM.SS):

12:00:00

Range: 00:00:00 to 23:59:59

IRIG-B SIGNAL TYPE:

NONE

Range: None, DC Shift, Amplitude Modulated

„ DEFAULT MESSAGES
„ [ENTER] for more

GENERATOR STATUS:

Stopped

Range: N/A

A:

0

B:

0

C:

0

Amps

Range: N/A

Vab:

0

Vbc:

0

Vca:

0

Volts

Range: N/A

FREQUENCY:

0.00 Hz

Range: N/A

POWER FACTOR:

0.00

Range: N/A

REAL POWER:

0 MW

Range: N/A

REACTIVE POWER

0 Mvar

Range: N/A

DATE: 01/01/1995

TIME: 12:00:00

Range: N/A

GE MULTILIN

489 GENERATOR RELAY

Range: N/A

ENTER

ESCAPE

р

р

MESSAGE

ESCAPE

MESSAGE

ESCAPE

ENTER

ESCAPE

р

р

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE