3 fault setup, 3 fault setup -80 – GE 489 User Manual

Page 130

Advertising
background image

4-80

489 Generator Management Relay

GE Multilin

4.13 S12 TESTING

4 SETPOINTS

4

4.13.3 FAULT SETUP

PATH: SETPOINTS

ÖØ

S12 TESTING

ÖØ

FAULT SETUP

The values entered here are substituted for the measured values in the 489 when the

SIMULATION MODE

is "Simulate Fault".

„ FAULT SETUP
„ [ENTER] for more

FAULT Iphase

OUTPUT: 0.00 x CT

Range: 0.00 to 20.00

× CT in steps of 0.01

FAULT VOLTAGES

PHASE-N: 1.00 x Rated

Range: 0.00 to 1.50

× Rated in steps of 0.01

Entered as a phase-to-neutral quantity.

FAULT CURRENT

LAGS VOLTAGE:

Range: 0 to 359° in steps of 1

FAULT Iphase

NEUTRAL: 0.00 x CT

Range: 0.00 to 20.00

× CT in steps of 0.01

180° phase shift with respect to Iphase OUTPUT

FAULT CURRENT

GROUND: 0.00 x CT

Range: 0.00 to 20.00

× CT in steps of 0.01

CT is either XXX:1 or 50:0.025

FAULT VOLTAGE

NEUTRAL: 0 Vsec

Range: 0.0 to 100.0 Vsec in steps of 0.1

Fundamental value only in secondary volts

FAULT STATOR

RTD TEMP: 40°C

Range: –50 to 250°C in steps of 1

FAULT BEARING

RTD TEMP: 40°C

Range: –50 to 250°C in steps of 1

FAULT OTHER

RTD TEMP: 40°C

Range: –50 to 250°C in steps of 1

FAULT AMBIENT

RTD TEMP: 40°C

Range: –50 to 250°C in steps of 1

FAULT SYSTEM

FREQUENCY: 60.0 Hz

Range: 5.0 to 90.0 Hz in steps of 0.1

FAULT ANALOG

INPUT 1: 0%

Range: 0 to 100% in steps of 1

FAULT ANALOG

INPUT 2: 0%

Range: 0 to 100% in steps of 1

FAULT ANALOG

INPUT 3: 0%

Range: 0 to 100% in steps of 1

FAULT ANALOG

INPUT 4: 0%

Range: 0 to 100% in steps of 1

ENTER

ESCAPE

р

р

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

Advertising