GE Multilin

489 Generator Management Relay

6-23

6 COMMUNICATIONS

6.3 MODBUS MEMORY MAP

6

2023

OVERVOLTAGE ALARM DELAY

1 to 1200

1

s

F2

30

2024

OVERVOLTAGE ALARM EVENTS

0 to 1

1

F105

0

2025

OVERVOLTAGE TRIP

0 to 2

1

F115

0

2026

ASSIGN TRIP RELAYS (1-4)

0 to 3

1

F50

1

2027

OVERVOLTAGE TRIP PICKUP

101 to 150

1

× Rated

F3

120

2028

OVERVOLTAGE TRIP DELAY

1 to 100

1

s

F2

10

2029

OVERVOLTAGE CURVE RESET RATE

0 to 9999

1

s

F2

14

202A

OVERVOLTAGE CURVE ELEMENT

0 to 1

1

F208

0

VOLTAGE ELEMENTS / VOLTS/HERTZ

2040

VOLTS/HERTZ ALARM

0 to 2

1

F115

0

2041

ASSIGN ALARM RELAYS (2-5)

1 to 4

1

F50

16

2042

VOLTS/HERTZ ALARM PICKUP

50 to 199

1

× Nominal

F3

100

2043

VOLTS/HERTZ ALARM DELAY

1 to 1500

1

s

F2

30

2044

VOLTS/HERTZ ALARM EVENTS

0 to 1

1

F105

0

2045

VOLTS/HERTZ TRIP

0 to 2

1

F115

0

2046

ASSIGN TRIP RELAYS (1-4)

0 to 3

1

F50

1

2047

VOLTS/HERTZ TRIP PICKUP

50 to 199

1

× Nominal

F3

100

2048

VOLTS/HERTZ TRIP DELAY

1 to 1500

1

s

F2

10

2049

VOLTS/HERTZ CURVE RESET RATE

0 to 9999

1

s

F2

14

204A

VOLTS/HERTZ TRIP ELEMENT

0 to 3

1

F211

0

VOLTAGE ELEMENTS / PHASE REVERSAL

2060

PHASE REVERSAL TRIP

0 to 2

1

F115

0

2061

ASSIGN TRIP RELAYS (1-4)

0 to 3

1

F50

1

VOLTAGE ELEMENTS / UNDERFREQUENCY

2080

BLOCK UNDERFREQUENCY FROM ONLINE

0 to 5

1

s

F1

1

2081

VOLTAGE LEVEL CUTOFF

50 to 99

1

× Rated

F3

50

2082

UNDERFREQUENCY ALARM

0 to 2

1

F115

0

2083

ASSIGN ALARM RELAYS (2-5)

1 to 4

1

F50

16

2084

UNDERFREQUENCY ALARM LEVEL

2000 to 6000

1

Hz

F3

5950

2085

UNDERFREQUENCY ALARM DELAY

1 to 50000

1

s

F2

50

2086

UNDERFREQUENCY ALARM EVENTS

0 to 1

1

F105

0

2087

UNDERFREQUENCY TRIP

0 to 2

1

F115

0

2088

ASSIGN TRIP RELAYS (1-4)

0 to 3

1

F50

1

2089

UNDERFREQUENCY TRIP LEVEL1

2000 to 6000

1

Hz

F3

5950

208A

UNDERFREQUENCY TRIP DELAY1

1 to 50000

1

s

F2

600

208B

UNDERFREQUENCY TRIP LEVEL2

2000 to 6000

1

Hz

F3

5800

208C

UNDERFREQUENCY TRIP DELAY2

1 to 50000

1

s

F2

300

VOLTAGE ELEMENTS / OVERFREQUENCY

20A0

BLOCK OVERFREQUENCY FROM ONLINE

0 to 5

1

s

F1

1

20A1

VOLTAGE LEVEL CUTOFF

50 to 99

1

× Rated

F3

50

20A2

OVERFREQUENCY ALARM

0 to 2

1

F115

0

20A3

ASSIGN ALARM RELAYS (2-5)

1 to 4

1

F50

16

20A4

OVERFREQUENCY ALARM LEVEL

2501 to 7000

1

Hz

F3

6050

20A5

OVERFREQUENCY ALARM DELAY

1 to 50000

1

s

F2

50

20A6

OVERFREQUENCY ALARM EVENTS

0 to 1

1

F105

0

20A7

OVERFREQUENCY TRIP

0 to 2

1

F115

0

20A8

ASSIGN TRIP RELAYS (1-4)

0 to 3

1

F50

1

20A9

OVERFREQUENCY TRIP LEVEL1

2501 to 7000

1

Hz

F3

6050

20AA

OVERFREQUENCY TRIP DELAY1

1 to 50000

1

s

F2

600

20AB

OVERFREQUENCY TRIP LEVEL2

2501 to 7000

1

Hz

F3

6200

20AC

OVERFREQUENCY TRIP DELAY2

1 to 50000

1

s

F2

300

VOLTAGE ELEMENTS / NEUTRAL O/V (FUND)

20C0

NEUTRAL OVERVOLTAGE ALARM

0 to 2

1

F115

0

20C1

ASSIGN ALARM RELAYS (2-5)

1 to 4

1

F50

16

20C2

NEUTRAL O/V ALARM LEVEL

20 to 1000

1

V

F2

30

20C3

NEUTRAL OVERVOLTAGE ALARM DELAY

1 to 1200

1

s

F2

10

20C4

NEUTRAL OVERVOLTAGE ALARM EVENTS

0 to 1

1

F105

0

20C5

NEUTRAL OVERVOLTAGE TRIP

0 to 2

1

F115

0

20C6

ASSIGN TRIP RELAYS (1-4)

0 to 3

1

F50

1

20C7

NEUTRAL O/V TRIP LEVEL

20 to 1000

1

V

F2

50

20C8

NEUTRAL OVERVOLTAGE TRIP DELAY

1 to 1200

1

s

F2

10

20C9

SUPERVISE WITH DIGITAL INPUT

0 to 1

1

F103

0

20CA

NEUTRAL O/V CURVE RESET RATE

0 to 9999

1

s

F2

0

20CB

NEUTRAL O/V TRIP ELEMENT

0 to 1

1

F208

1

Table 6–1: 489 MEMORY MAP (SHEET 14 OF 24)

ADDR NAME

RANGE

STEP

UNITS

FORMAT

DEFAULT

1, 2, 3

See Table footnotes on page 6–33