7 TESTING

7.3 ADDITIONAL FUNCTIONAL TESTS

7

7.3.3 REACTIVE POWER ACCURACY

The specification for reactive power is

±1% of

Ч 2 Ч CT × VT × VT

full scale

at I

avg

< 2 × CT. Perform the steps below to

verify accuracy and trip element.

1.

Alter the following system setpoints:

S2 SYSTEM SETUP

Ö

CURRENT SENSING

Ö

PHASE CT PRIMARY:

"5000"

S2 SYSTEM SETUP

ÖØ

VOLTAGE SENSING

Ö

VT CONNECTION TYPE:

"Wye"

S2 SYSTEM SETUP

ÖØ

VOLTAGE SENSING

ÖØ

VOLTAGE TRANSFORMER RATIO:

"100:1"

S2 SYSTEM SETUP

ÖØ

GEN. PARAMETERS

Ö

GENERATOR RATED MVA:

"100"

S2 SYSTEM SETUP

ÖØ

GEN. PARAMETERS

ÖØ

GENERATOR RATED POWER FACTOR:

"0.85"

S2 SYSTEM SETUP

ÖØ

GEN. PARAMETERS

ÖØ

GENERATOR VOLTAGE PHASE-PHASE:

"12000"

The rated reactive power is

.

2.

Alter the following reactive power setpoints:

S7 POWER ELEMENTS

Ö

REACTIVE POWER

ÖØ

REACTIVE POWER ALARM:

"Unlatched"

S7 POWER ELEMENTS

Ö

REACTIVE POWER

ÖØ

ASSIGN ALARM RELAYS(2-5):

"---5"

S7 POWER ELEMENTS

Ö

REACTIVE POWER

ÖØ

POSTIVE Mvar ALARM LEVEL:

"0.6 x Rated"

S7 POWER ELEMENTS

Ö

REACTIVE POWER

ÖØ

NEGATIVE Mvar ALARM LEVEL:

"0.6 x Rated"

S7 POWER ELEMENTS

Ö

REACTIVE POWER

ÖØ

REACTIVE POWER ALARM DELAY:

"5 s"

S7 POWER ELEMENTS

Ö

REACTIVE POWER

ÖØ

REACTIVE POWER ALARM EVENT:

"On"

S7 POWER ELEMENTS

Ö

REACTIVE POWER

ÖØ

REACTIVE POWER TRIP: "

Unlatched"

S7 POWER ELEMENTS

Ö

REACTIVE POWER

ÖØ

ASSIGN TRIP RELAYS(1-4):

"1---"

S7 POWER ELEMENTS

Ö

REACTIVE POWER

ÖØ

POSTIVE Mvar TRIP LEVEL:

"0.75 x Rated"

S7 POWER ELEMENTS

Ö

REACTIVE POWER

ÖØ

NEGATIVE Mvar TRIP LEVEL:

"0.75 x Rated"

S7 POWER ELEMENTS

Ö

REACTIVE POWER

ÖØ

REACTIVE POWER TRIP DELAY:

"10 s"

3.

Inject current and apply voltage as per the table below. Verify the alarm/trip elements and the accuracy of the mea-
sured values. View the measured values in:

A2 METERING DATA

Ö

POWER METERING

4.

View the Event Records in

A5 EVENT RECORD

CURRENT/

VOLTAGE

MVAR

ALARM

TRIP

EXPECTED TOLERANCE MEASURED EXPECTED OBSERVED

DELAY

EXPECTED OBSERVED

DELAY

Vab=120V

∠0°

Vbc=120V

∠120°lag

Vca=120V

∠240°lag

Ian=5 A

∠10°lag

Ibn=5 A

∠130°lag

Icn=5 A

∠250°lag

18

13 to 23

N/A

N/A

Vab=120V

∠0°

Vbc=120V

∠120°lag

Vca=120V

∠240°lag

Ian=5 A

∠340°lag

Ibn=5 A

∠100°lag

Icn=5 A

∠220°lag

–35

–40 to –30

N/A

Vab=120V

∠0°

Vbc=120V

∠120°lag

Vca=120V

∠240°lag

Ian=5 A

∠330°lag

Ibn=5 A

∠90°lag

Icn=5 A

∠210°lag

–52

–57 to –47

Vab=120V

∠0°

Vbc=120V

∠120°lag

Vca=120V

∠240°lag

Ian=5 A

∠30°lag

Ibn=5 A

∠150°lag

Icn=5 A

∠270°lag

52

47 to 57

: Activated, : Not Activated

3

100

cos

1

0.85

(

)

(

)

sin

52.7 Mvar

±

=