4-39

4 SETPOINTS

4.7 S6 VOLTAGE ELEMENTS

4

4.7.7 NEUTRAL OVERVOLTAGE (FUNDAMENTAL)

PATH: SETPOINTS

ÖØ

S6 VOLTAGE ELEMENTS

ÖØ

O/V (FUND)

The neutral overvoltage function responds to fundamental frequency voltage at the generator neutral. It provides ground
fault protection for approximately 95% of the stator windings. 100% protection is provided when this element is used in con-
junction with the Neutral Undervoltage (3rd harmonic) function. The alarm element is definite time and the trip element can
be either definite time or an inverse time curve. When the neutral voltage rises above the pickup level the element will begin
to time out. If the time expires an alarm or trip will occur. The reset rate is a linear reset time from the threshold of trip. The
alarm and trip levels are programmable in terms of Neutral VT secondary voltage.

„ NEUTRAL O/V (FUND)
„ [ENTER] for more

SUPERVISE WITH

DIGITAL INPUT: No

Range: Yes, No. Seen only if a digital input assigned to

GROUND SWITCH STATUS

NEUTRAL OVERVOLTAGE

ALARM: Off

Range: Off, Latched, Unlatched

ASSIGN ALARM

RELAYS (2-5): ---5

Range: Any combination of Relays 2 to 5

NEUTRAL O/V ALARM

LEVEL: 3.0 Vsec

Range: 2.0 to 100.0 Vsec in steps of 0.1

NEUTRAL OVERVOLTAGE

ALARM DELAY: 1.0 s

Range: 0.1 to 120.0 s in steps of 0.1

NEUTRAL OVERVOLTAGE

ALARM EVENTS: Off

Range: On, Off

NEUTRAL OVERVOLTAGE

TRIP: Off

Range: Off, Latched, Unlatched

ASSIGN TRIP

RELAYS (1-4): 1---

Range: Any combination of Relays 1 to 4

NEUTRAL O/V TRIP

LEVEL: 5.0 Vsec

Range: 2.0 to 100.0 Vsec in steps of 0.1

NEUTRAL OVERVOLTAGE

TRIP DELAY: 1.0 s

Range: 0.1 to 120.0 s in steps of 0.1

NEUTRAL O/V CURVE

RESET RATE: 0.0

Range: 0.0 to 999.9 in steps of 0.1

NEUTRAL O/V TRIP

ELEMENT: Definite Time

Range: Curve, Definite Time

The formula for the curve is:

(EQ 4.20)

where

T = trip time in seconds
D =

NEUTRAL OVERVOLTAGE TRIP DELAY

setpoint

V = neutral voltage
V

pickup

=

NEUTRAL O/V TRIP LEVEL

setpoint

The neutral overvoltage curves are shown on the right.
Refer to Appendix B for Application Notes.

ENTER

ESCAPE

р

р

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

T

D

V V

pickup

(

) 1

-----------------------------------------

=

when V V

pickup

>

808741A1.CDR

0.1

1

10

100

1000

1

1.1

1.2

1.3

1.4

1.5

1.6

1.7

1.8

1.9

2

Multiples of Overvoltage Pickup

10

3

1

0.3

0.1

T

im

et

oT

ri

p

(s

e

c

ond

s)

T

IM

E

D

E

LA

Y

S

E

TT

IN

G

Advertising