7 digital inputs and trip coil supervision, 8 analog inputs and outputs, Digital inputs and trip coil supervision -7 – GE 489 User Manual

Page 219: Analog inputs and outputs -7

Advertising
background image

GE Multilin

489 Generator Management Relay

7-7

7 TESTING

7.2 HARDWARE FUNCTIONAL TESTS

7

7.2.7 DIGITAL INPUTS AND TRIP COIL SUPERVISION

The digital inputs and trip coil supervision can be verified easily with a simple switch or pushbutton. Verify the SWITCH
+24 V DC with a voltmeter. Perform the steps below to verify functionality of the digital inputs.

1.

Open switches of all of the digital inputs and the trip coil supervision circuit.

2.

View the status of the digital inputs and trip coil supervision in:

A1 STATUS

ÖØ

DIGITAL INPUTS

3.

Close switches of all of the digital inputs and the trip coil supervision circuit.

4.

View the status of the digital inputs and trip coil supervision in:

A1 STATUS

ÖØ

DIGITAL INPUTS

7.2.8 ANALOG INPUTS AND OUTPUTS

The specification for analog input and analog output accuracy is

±1% of full scale. Perform the steps below to verify accu-

racy. Verify the Analog Input +24 V DC with a voltmeter.

4 to 20 mA INPUTS:

1.

Alter the following setpoints:

S11 ANALOG I/O

ÖØ

ANALOG INPUT1

Ö

ANALOG INPUT1:

"4-20 mA"

S11 ANALOG I/O

ÖØ

ANALOG INPUT1

ÖØ

ANALOG INPUT1 MINIMUM:

"0"

S11 ANALOG I/O

ÖØ

ANALOG INPUT1

ÖØ

ANALOG INPUT1 MAXIMUM:

"1000" (repeat all for Analog Inputs 2 to 4)

2.

Analog output values should be

±0.2 mA on the ammeter. Measured analog input values should be ±10 units. Force

the analog outputs using the following setpoints:

S12 TESTING

ÖØ

TEST ANALOG OUTPUT

Ö

FORCE ANALOG OUTPUTS FUNCTION:

"Enabled"

S12 TESTING

ÖØ

TEST ANALOG OUTPUT

ÖØ

ANALOG OUTPUT 1 FORCED VALUE:

"0%" (enter %, repeat for Outputs 2 to 4)

3.

Verify the ammeter readings and the measured analog input readings. For the purposes of testing, the analog input is
fed in from the analog output (see Figure 7–1: Secondary Current Injection Testing). View the measured values in:

A2 METERING DATA

Ö

ANALOG INPUTS

INPUT

EXPECTED STATUS

(SWITCH OPEN)

PASS

FAIL

EXPECTED STATUS

(SWITCH CLOSED)

PASS

FAIL

ACCESS

Open

Shorted

BREAKER STATUS

Open

Shorted

ASSIGNABLE INPUT 1

Open

Shorted

ASSIGNABLE INPUT 2

Open

Shorted

ASSIGNABLE INPUT 3

Open

Shorted

ASSIGNABLE INPUT 4

Open

Shorted

ASSIGNABLE INPUT 5

Open

Shorted

ASSIGNABLE INPUT 6

Open

Shorted

ASSIGNABLE INPUT 7

Open

Shorted

TRIP COIL SUPERVISION

No Coil

Coil

ANALOG

OUTPUT

FORCE

VALUE

EXPECTED

AMMETER

READING

MEASURED AMMETER READING

(MA)

EXPECTED

ANALOG INPUT

READING

MEASURED ANALOG INPUT

READING (UNITS)

1

2

3

4

1

2

3

4

0%

4 mA

0 units

25%

8 mA

250 units

50%

12 mA

500 units

75%

16 mA

750 units

100%

20 mA

1000 units