6.3 MODBUS MEMORY MAP

6

26A5

RTD #11 TRIP

0 to 2

1

F115

0

26A6

RTD #11 TRIP VOTING

1 to 12

1

F122

11

26A7

ASSIGN TRIP RELAYS (1-4)

0 to 3

1

F50

1

26A8

RTD #11 TRIP TEMPERATURE

1 to 250

1

°C

F1

90

26A9

RTD #11 NAME

0 to 8

1

F22

_

RTD TEMPERATURE / RTD #12

26E0

RTD #12 APPLICATION

0 to 4

1

F121

3

26E1

RTD #12 ALARM

0 to 2

1

F115

0

26E2

ASSIGN ALARM RELAYS (2-5)

1 to 4

1

F50

16

26E3

RTD #12 ALARM TEMPERATURE

1 to 250

1

°C

F1

60

26E4

RTD #12 ALARM EVENTS

0 to 1

1

F105

0

26E5

RTD #12 TRIP

0 to 2

1

F115

0

26E6

RTD #12 TRIP VOTING

1 to 12

1

F122

12

26E7

ASSIGN TRIP RELAYS (1-4)

0 to 3

1

F50

1

26E8

RTD #12 TRIP TEMPERATURE

1 to 250

1

°C

F1

80

26E9

RTD #12 NAME

0 to 8

1

F22

_

RTD TEMPERATURE / OPEN RTD SENSOR

2720

OPEN RTD SENSOR ALARM

0 to 2

1

F115

0

2721

ASSIGN ALARM RELAYS (2-5)

1 to 4

1

F50

16

2722

OPEN RTD SENSOR ALARM EVENTS

0 to 1

1

F105

0

RTD TEMPERATURE / RTD SHORT/LOW TEMP

2740

RTD SHORT/LOW TEMP ALARM

0 to 2

1

F115

0

2741

ASSIGN ALARM RELAYS (2-5)

1 to 4

1

F50

16

2742

RTD SHORT/LOW TEMP ALARM EVENTS

0 to 1

1

F105

0

THERMAL MODEL / MODEL SETUP

2800

ENABLE THERMAL MODEL

0 to 1

1

F103

0

2801

OVERLOAD PICKUP LEVEL

101 to 125

1

× FLA

F3

101

2802

UNBALANCE BIAS K FACTOR

0 to 12

1

F1

0

2803

COOL TIME CONSTANT ONLINE

0 to 500

1

min

F1

15

2804

COOL TIME CONSTANT OFFLINE

0 to 500

1

min

F1

30

2805

HOT/COLD SAFE STALL RATIO

1 to 100

1

F3

100

2806

ENABLE RTD BIASING

0 to 1

1

F103

0

2807

RTD BIAS MINIMUM

0 to 250

1

°C

F1

40

2808

RTD BIAS CENTER POINT

0 to 250

1

°C

F1

130

2809

RTD BIAS MAXIMUM

0 to 250

1

°C

F1

155

280A

SELECT CURVE STYLE

0 to 2

1

F142

0

280B

STANDARD OVERLOAD CURVE NUMBER

1 to 15

1

F1

4

280C

TIME TO TRIP AT 1.01

× FLA

5 to 999999

1

s

F10

5

280E

TIME TO TRIP AT 1.05

× FLA

5 to 999999

1

s

F10

5

2810

TIME TO TRIP AT 1.10

× FLA

5 to 999999

1

s

F10

5

2812

TIME TO TRIP AT 1.20

× FLA

5 to 999999

1

s

F10

5

2814

TIME TO TRIP AT 1.30

× FLA

5 to 999999

1

s

F10

5

2816

TIME TO TRIP AT 1.40

× FLA

5 to 999999

1

s

F10

5

2818

TIME TO TRIP AT 1.50

× FLA

5 to 999999

1

s

F10

5

281A

TIME TO TRIP AT 1.75

× FLA

5 to 999999

1

s

F10

5

281C

TIME TO TRIP AT 2.00

× FLA

5 to 999999

1

s

F10

5

281E

TIME TO TRIP AT 2.25

× FLA

5 to 999999

1

s

F10

5

2820

TIME TO TRIP AT 2.50

× FLA

5 to 999999

1

s

F10

5

2822

TIME TO TRIP AT 2.75

× FLA

5 to 999999

1

s

F10

5

2824

TIME TO TRIP AT 3.00

× FLA

5 to 999999

1

s

F10

5

2826

TIME TO TRIP AT 3.25

× FLA

5 to 999999

1

s

F10

5

2828

TIME TO TRIP AT 3.50

× FLA

5 to 999999

1

s

F10

5

282A

TIME TO TRIP AT 3.75

× FLA

5 to 999999

1

s

F10

5

282C

TIME TO TRIP AT 4.00

× FLA

5 to 999999

1

s

F10

5

282E

TIME TO TRIP AT 4.25

× FLA

5 to 999999

1

s

F10

5

2830

TIME TO TRIP AT 4.50

× FLA

5 to 999999

1

s

F10

5

2832

TIME TO TRIP AT 4.75

× FLA

5 to 999999

1

s

F10

5

2834

TIME TO TRIP AT 5.00

× FLA

5 to 999999

1

s

F10

5

2836

TIME TO TRIP AT 5.50

× FLA

5 to 999999

1

s

F10

5

2838

TIME TO TRIP AT 6.00

× FLA

5 to 999999

1

s

F10

5

283A

TIME TO TRIP AT 6.50

× FLA

5 to 999999

1

s

F10

5

283C

TIME TO TRIP AT 7.00

× FLA

5 to 999999

1

s

F10

5

283E

TIME TO TRIP AT 7.50

× FLA

5 to 999999

1

s

F10

5

2840

TIME TO TRIP AT 8.00

× FLA

5 to 999999

1

s

F10

5

2842

TIME TO TRIP AT 10.0

× FLA

5 to 999999

1

s

F10

5

2844

TIME TO TRIP AT 15.0

× FLA

5 to 999999

1

s

F10

5

Table 6–1: 489 MEMORY MAP (SHEET 18 OF 24)