3 alarm status, Alarm status -4 – GE 489 User Manual

Page 136

Advertising
background image

5-4

489 Generator Management Relay

GE Multilin

5.2 A1 STATUS

5 ACTUAL VALUES

5

Immediately prior to issuing a trip, the 489 takes a snapshot of generator parameters and stores them as pre-trip values;
this allows for troubleshooting after the trip occurs. The cause of last trip message is updated with the current trip and the
screen defaults to that message. All trip features are automatically logged as date and time stamped events as they occur.
This information can be cleared using the

S1 489 SETUP

ÖØ

CLEAR DATA

ÖØ

CLEAR LAST TRIP DATA

setpoint. If the cause of

last trip is "No Trip To Date", the subsequent pretrip messages will not appear. Last Trip Data will not update if a digital input
programmed as Test Input is shorted.

5.2.3 ALARM STATUS

PATH: ACTUAL VALUES

Ö

A1 STATUS

ÖØ

ALARM STATUS

NEUTRAL VOLT (3rd)

PRETRIP: 0.0 V

Range: 0.0 to 25000.0 V

Seen only if there is a neutral voltage
transformer.

REAL POWER (MW)

PRETRIP: 0.000

Range: 0.000 to ±2000.000 MW

Not seen if

VT CONNECTION

is "None"

REACTIVE POWER Mvar

PRETRIP: 0.00 Hz

Range: 0.000 to ±2000.000 Mvar

Not seen if

VT CONNECTION

is "None"

APPARENT POWER MVA

PRETRIP: 0.00 Hz

Range: 0.000 to ±2000.000 MVA

Not seen if

VT CONNECTION

is "None"

HOTTEST STATOR RTD

RTD #1: 0°C PreTrip

Range: –50 to 250°C

Seen only if at least one RTD is "Stator"

HOTTEST BEARING RTD

RTD #7: 0°C PreTrip

Range: –50 to 250°C

Seen only if at least one RTD is "Bearing"

HOTTEST OTHER RTD

RTD #11: 0°C PreTrip

Range: –50 to 250°C

Seen only if at least one RTD is "Other"

AMBIENT RTD

RTD#12: 0°C PreTrip

Range: –50 to 250°C

Seen only if at least one RTD is Ambient

ANALOG INPUT 1

PreTrip: 0 Units

Range: –50000 to 50000

Not seen if

VT CONNECTION

is "None"

ANALOG INPUT 2

PreTrip: 0 Units

Range: –50000 to 50000

Not seen if

VT CONNECTION

is "None"

ANALOG INPUT 3

PreTrip: 0 Units

Range: –50000 to 50000

Not seen if

VT CONNECTION

is "None"

ANALOG INPUT 4

PreTrip: 0 Units

Range: –50000 to 50000

Not seen if

VT CONNECTION

is "None"

Vab/Iab PreTrip:

0.0

Ωsec.

Range: 0 to 65535

Ωsec; 0 to 359°

Seen only if Loss of Excitation is enabled

„ ALARM STATUS
„ [ENTER] for more

NO ALARMS

Range: N/A

Message seen when no alarms are active

Input A ALARM

STATUS: Active

Range: Active, Latched. The first line of this alarm

message reflects the Input Name as
programmed. Status is Active if the condition
that caused the alarm is still present

Input B ALARM

STATUS: Active

Range: see Input A ALARM STATUS

Input C ALARM

STATUS: Active

Range: see Input A ALARM STATUS

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

ENTER

ESCAPE

р

р

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE