GE Multilin

489 Generator Management Relay

4-69

4 SETPOINTS

4.11 S10 MONITORING

4

4.11S10 MONITORING

4.11.1 TRIP COUNTER

PATH: SETPOINTS

ÖØ

S10 MONITORING

Ö

TRIP COUNTER

When enabled, a trip counter alarm will occur when the

TRIP COUNTER ALARM LEVEL

is reached. The trip counter must be

cleared or the alarm level raised and the reset key must be pressed (if the alarm was latched) to reset the alarm.

For example, it might be useful to set a Trip Counter alarm at 100 trips, prompting the operator or supervisor to investigate
the type of trips that have occurred. A breakdown of trips by type may be found in the

A4 MAINTENANCE

ÖØ

TRIP COUNTERS

actual values page. If a trend is detected, it would warrant further investigation.

4.11.2 BREAKER FAILURE

PATH: SETPOINTS

ÖØ

S10 MONITORING

ÖØ

BREAKER FAILURE

If the breaker failure alarm feature may be enabled as latched or unlatched. If the R1 Trip output relay is operated and the
generator current measured at any of the three output CTs is above the level programmed for the period of time specified
by the delay, a breaker failure alarm will occur. The time delay should be slightly longer than the breaker clearing time.

„ TRIP COUNTER
„ [ENTER] for more

TRIP COUNTER

ALARM: Off

Range: Off, Latched, Unlatched

ASSIGN ALARM

RELAYS (2-5): ---5

Range: Any combination of Relays 2 to 5

TRIP COUNTER ALARM

LEVEL: 25 Trips

Range: 1 to 50000 Trips in steps of 1

TRIP COUNTER ALARM

EVENTS: Off

Range: On, Off

„ BREAKER FAILURE
„ [ENTER] for more

BREAKER FAILURE

ALARM: Off

Range: Off, Latched, Unlatched

ASSIGN ALARM

RELAYS (2-5): ---5

Range: Any combination of Relays 2 to 5

BREAKER FAILURE

LEVEL: 1.00 x CT

Range: 0.05 to 20.00

× CT in steps of 0.01

BREAKER FAILURE

DELAY: 100 ms

Range: 10 to 1000 ms in steps of 10

BREAKER FAILURE

ALARM EVENTS: Off

Range: On, Off

ENTER