GE 489 User Manual

Page 16

Advertising
background image

1-8

489 Generator Management Relay

GE Multilin

1.2 SPECIFICATIONS

1 INTRODUCTION

1

At temperatures lower than –20°C, the LCD contrast
may be impaired.

LONG-TERM STORAGE

Environment:

In addition to the above environmental
considerations, the relay should be
stored in an environment that is dry, cor-
rosive-free, and not in direct sunlight.

Correct storage:

Prevents premature component failures
caused by environmental factors such as
moisture or corrosive gases. Exposure
to high humidity or corrosive environ-
ments will prematurely degrade the elec-
tronic components in any electronic
device regardless of its use or manufac-
turer, unless specific precautions, such
as those mentioned in the Environmental
section above, are taken.

It is recommended that all relays be powered up once
per year, for one hour continuously, to avoid
deterioration of electrolytic capacitors and
subsequent relay failure.

CASE

Drawout:

Fully drawout (Automatic CT shorts)

Seal:

Seal provision

Door:

Dust tight door

Mounting:

Panel or 19" rack mount

IP Class:

IP20-X

PRODUCTION TESTS

Thermal Cycling:

Operational test at ambient, reducing to
–40°C and then increasing to 60°C

Dielectric Strength:

1.9 kV AC for 1 second or 1.6 kV AC for
1 minute, per UL 508.

DO NOT CONNECT FILTER GROUND TO
SAFETY GROUND DURING ANY PRODUCTION
TESTS!

FUSE

Current Rating:

3.15 A

Type:

5

× 20 mm Slo-Blo Littelfuse, High

Breaking Capacity

Model#:

215.315

An external fuse must be used if supply voltage
exceeds 250V

TYPE TESTS

Dielectric Strength:

Per IEC 255-5 and ANSI/IEEE C37.90.
2.0 kV for 1 minute from relays, CTs,
VTs, power supply to Safety Ground

DO NOT CONNECT FILTER GROUND TO SAFETY
GROUND DURING TEST

Insulation Resistance:

IEC255-5 500 V DC, from relays, CTs,
VTs, power supply to Safety Ground

DO NOT CONNECT FILTER GROUND TO
SAFETY GROUND DURING TEST

Transients:

ANSI C37.90.1 oscillatory (2.5 kV/
1 MHz); ANSI C37.90.1 Fast Rise (5 kV/
10 ns); Ontario Hydro A-28M-82;
IEC255-4 Impulse/High Frequency Dis-
turbance Class III Level

Impulse Test:

IEC 255-5 0.5 Joule 5 kV

RFI:

50 MHz / 15 W Transmitter

EMI:

C37.90.2 Electromagnetic Interference
at 150 MHz and 450 MHz, 10V/m

Static:

IEC 801-2 Static Discharge

Humidity:

90% non-condensing

Temperature:

–40°C to +60°C ambient

Environment:

IEC 68-2-38 Temperature/Humidity cycle

Vibration:

Sinusoidal Vibration 8.0 g for 72 hrs.

PACKAGING

Shipping Box:

12”

Ч 11” Ч 10” (W × H × D)

30.5cm

× 27.9cm × 25.4cm

Shipping Weight:

17 lbs Max / 7.7 kg

CERTIFICATION

ISO:

Manufactured under an ISO9001 regis-
tered system.

UL:

UL

CSA:

CSA

CE:

Conforms to IEC 947-1, IEC 1010-1

NOTE

WARNING

WARNING

WARNING

WARNING

WARNING

Advertising