4.4 S3 DIGITAL INPUTS

4 SETPOINTS

4

4.4.9 FIELD-BREAKER DISCREPANCY

PATH: SETPOINTS

ÖØ

S3 DIGITAL INPUTS

ÖØ

FIELD-BKR DISCREP.

The field-breaker discrepancy function is intended for use with synchronous generators. If a digital input is assigned to this
function, any time the field status contact indicates the field is not applied and the breaker status input indicates that the
generator is online, a trip will occur once the time delay has expired. The time delay should be used to prevent possible nui-
sance tripping during shutdown. The field status contact may be chosen as "Auxiliary a", open signifying the field breaker or
contactor is open and shorted signifying the field breaker or contactor is closed. Conversely, the field status contact may be
chosen as "Auxiliary b", shorted signifying the field breaker or contactor is open and open signifying it is closed.

4.4.10 TACHOMETER

PATH: SETPOINTS

ÖØ

S3 DIGITAL INPUTS

ÖØ

TACHOMETER

„ FIELD-BKR DISCREP.
„ [ENTER] for more

ASSIGN DIGITAL

INPUT: None

Range: None, Input 1 to Input 7. If an input is assigned to

the Tachometer, it may not be used here.

FIELD STATUS

CONTACT: Auxiliary a

Range: Auxiliary a, Auxiliary b

ASSIGN TRIP

RELAYS (1-4): 1---

Range: Any combination of Relays 1 to 4

FIELD-BKR DISCREP.

TRIP DELAY: 1.0 s

Range: 0.1 to 500.0 s in steps of 0.1

„ TACHOMETER
„ [ENTER] for more

ASSIGN DIGITAL

INPUT: None

Range: None, Inputs 4 to 7. Only Digital Inputs 4 to 7

may be assigned to the Tachometer

RATED SPEED:

3600 RPM

Range: 100 to 3600 RPM in steps of 1

TACHOMETER

ALARM: Off

Range: Off, Latched, Unlatched

ASSIGN ALARM

RELAYS (2-5): ---5

Range: Any combination of Relays 2 to 5

TACHOMETER ALARM

SPEED: 110% Rated

Range: 101 to 175% in steps of 1

TACHOMETER ALARM

DELAY: 1 s

Range: 1 to 250 s in steps of 1

TACHOMETER ALARM

EVENTS: Off

Range: On, Off

TACHOMETER

TRIP: Off

Range: Off, Latched, Unlatched

ASSIGN TRIP

RELAYS (1-4): 1---

Range: Any combination of Relays 1 to 4

TACHOMETER TRIP

SPEED: 110% Rated

Range: 101 to 175% in steps of 1

TACHOMETER TRIP

DELAY: 1 s

Range: 1 to 250 s in steps of 1

ENTER

ESCAPE

р

р

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

ENTER

ESCAPE

р

р

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

Advertising