489 Generator Management Relay

5-5

5 ACTUAL VALUES

5.2 A1 STATUS

5

Input D ALARM

STATUS: Active

Range: see Input A ALARM STATUS

Input E ALARM

STATUS: Active

Range: see Input A ALARM STATUS

Input F ALARM

STATUS: Active

Range: see Input A ALARM STATUS

Input G ALARM

STATUS: Active

Range: see Input A ALARM STATUS

TACHOMETER

ALARM: 3000 RPM

Range: 0 to 3600 RPM. The current Tachometer

Digital Input value is shown here

OVERCURRENT

ALARM: 10.00 x FLA

Range: 0.00 to 20.00

× FLA

The overcurrent level is shown here.

NEG. SEQ. CURRENT

ALARM: 15% FLA

Range: 0 to 100% FLA. Reflects the present negative-

sequence current level.

GROUND OVERCURRENT

ALARM: 5.00 A

Range: 0.00 to 200000.00 A. Seen only if the GE HGF

CT is used. Reflects the present ground
current level.

GROUND DIRECTIONAL

ALARM: 5.00 A

Range: 0.00 to 200000.00 A

UNDERVOLTAGE ALARM

Vab= 3245 V

78% Rated

Range: 0 to 20000 V; 50 to 99% of Rated. The lowest

phase-to-phase voltage value is shown here

OVERVOLTAGE ALARM

Vab= 4992 V

120% Rated

Range: 0 to 20000 V; 101 to 150% of Rated. The

lowest phase-to-phase voltage is shown here

VOLTS/HERTZ ALARM

PER UNIT V/Hz: 1.15

Range: 0.00 to 2.00. The present V/Hz value is shown

here. Not seen if VT CONNECTION is None.

UNDERFREQUENCY

ALARM: 59.4 Hz

Range: 0.00 to 90.00 Hz

Reflects the present voltage frequency value.

OVERFREQUENCY

ALARM: 60.6 Hz

Range: 0.00 to 90.00 Hz

Reflects the present voltage frequency value.

NEUTRAL O/V (FUND)

ALARM: 0.0 V

Range: 0.0 to 25000.0 V. The present fundamental

neutral voltage value is displayed here.

NEUTRAL U/V (3rd)

ALARM: 0.0 V

Range: 0.0 to 25000.0 V. The present 3rd harmonic

neutral voltage value is displayed here.

REACTIVE POWER Mvar

ALARM: +20.000

Range: –2000.000 to +2000.000 Mvar

The current Mvar value is shown here

REVERSE POWER

ALARM: –20.000 MW

Range: –2000.000 to +2000.000 MW

The current MW value is shown here

LOW FORWARD POWER

ALARM: –20.000 MW

Range: –2000.000 to +2000.000 MW

The current MW value is shown here

STATOR RTD #1

ALARM: 135°C

Range: –50 to +250°C. The present RTD temperature

is shown. Reflects programmed RTD Name.

OPEN SENSOR ALARM:

RTD # 1 2 3 4 5 6 ...

Range: RTDs 1 to 12. Reflects the RTD(s) that caused

the open sensor alarm.

SHORT/LOW TEMP ALARM

RTD # 7 8 9 10 11 ...

Range: RTDs 1 to 12. Reflects the RTD(s) that caused

the short/low temp. alarm.

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

Advertising