GE Multilin

489 Generator Management Relay

4-33

4 SETPOINTS

4.7 S6 VOLTAGE ELEMENTS

4

4.7S6 VOLTAGE ELEMENTS

4.7.1 UNDERVOLTAGE

PATH: SETPOINTS

ÖØ

S6 VOLTAGE ELEMENTS

Ö

UNDERVOLTAGE

The undervoltage elements may be used for protection of the generator and/or its auxiliary equipment during prolonged
undervoltage conditions. They are active only when the generator is online. The alarm element is definite time and the trip
element can be definite time or a curve. When the magnitude of the average phase-phase voltage is less than the pickup

×

the generator rated phase-phase voltage, the element will begin to time out. If the time expires, a trip or alarm will occur.

„ UNDERVOLTAGE
„ [ENTER] for more

UNDERVOLTAGE

ALARM: Off

Range: Off, Latched, Unlatched

ASSIGN ALARM

RELAYS (2-5): ---5

Range: Any combination of Relays 2 to 5

UNDERVOLTAGE ALARM

PICKUP: 0.85 x Rated

Range: 0.50 to 0.99

× Rated in steps of 0.01

UNDERVOLTAGE ALARM

DELAY: 3.0 s

Range: 0.2 to 120.0 s in steps of 0.1

UNDERVOLTAGE ALARM

EVENTS: Off

Range: On, Off

UNDERVOLTAGE

TRIP: Off

Range: Off, Latched, Unlatched

ASSIGN TRIP

RELAYS (1-4): 1---

Range: Any combination of Relays 1 to 4

UNDERVOLTAGE TRIP

PICKUP: 0.80 x Rated

Range: 0.50 to 0.99

× Rated in steps of 0.01

UNDERVOLTAGE TRIP

DELAY: 1.0 s

Range: 0.2 to 10.0 s in steps of 0.1

UNDERVOLTAGE CURVE

RESET RATE: 1.4 s

Range: 0.0 to 999.9 s in steps of 0.1

UNDERVOLTAGE CURVE

ELEMENT: Curve

Range: Curve, Definite Time

The curve reset rate is a linear reset time from the threshold
of trip. If the VT type is selected as None, VT fuse loss is
detected, or the magnitude of I

1

< 7.5% CT, the undervoltage

protection is disabled. The pickup levels are insensitive to
frequency over the range of 5 to 90 Hz.

The formula for the undervoltage curve is:

(EQ 4.18)

where: T = trip time in seconds

D =

UNDERVOLTAGE TRIP DELAY

setpoint

V = actual average phase-phase voltage
V

pickup

=

UNDERVOLTAGE TRIP PICKUP

setpoint

ENTER

ESCAPE

р

р

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

T

D

1 V V

pickup

------------------------------------

=

, when V V

pickup

<

808742A1.CDR

0.1

1

10

100

1000

0

0.2

0.4

0.6

0.8

1

Multiples of Undervoltage Pickup

10

3

1

0.3

T

IM

E

D

E

LA

Y

S

E

TT

IN

G

T

im

et

oT

ri

p

(s

e

c

ond

s)

Advertising