4.6 S5 CURRENT ELEMENTS

4 SETPOINTS

4

c) IEC CURVES

For European applications, the relay offers the four standard curves defined in IEC 255-4 and British standard BS142.
These are defined as IEC Curve A, IEC Curve B, IEC Curve C, and Short Inverse. The formula for these curves is:

(EQ 4.5)

where: T = Trip Time in seconds

M = Multiplier setpoint
I = Input Current
I

pickup

= Pickup Current setpoint

K, E = Constants

d) IAC CURVES

The curves for the General Electric type IAC relay family are derived from the formula:

(EQ 4.6)

where: T = Trip Time in seconds

M = Multiplier setpoint
I = Input Current
I

pickup

= Pickup Current setpoint

A, B, C, D, E = Constants

Table 4–3: IEC (BS) INVERSE TIME CURVE CONSTANTS

IEC (BS) CURVE SHAPE

CONSTANTS

K

E

IEC CURVE A (BS142)

0.140

0.020

IEC CURVE B (BS142)

13.500

1.000

IEC CURVE C (BS142)

80.000

2.000

SHORT INVERSE

0.050

0.040

Table 4–4: IAC INVERSE TIME CURVE CONSTANTS

IAC CURVE SHAPE

CONSTANTS

A

B

C

D

E

IAC EXTREME INVERSE

0.0040

0.6379

0.6200

1.7872

0.2461

IAC VERY INVERSE

0.0900

0.7955

0.1000

–1.2885

7.9586

IAC INVERSE

0.2078

0.8630

0.8000

–0.4180

0.1947

IAC SHORT INVERSE

0.0428

0.0609

0.6200

–0.0010

0.0221

T

M

K

I I

pickup

(

)

E

1

---------------------------------------

×

=

T

M

A

B

I I

pickup

(

) C

-------------------------------------

D

I I

pickup

(

) C

(

)

2

---------------------------------------------

E

I I

pickup

(

) C

(

)

3

---------------------------------------------

+

+

+

Ч

=