4 analog input / input change (objects 30/32), Analog input / input change (objects 30/32) -47 – GE 489 User Manual

Page 209

Advertising
background image

GE Multilin

489 Generator Management Relay

6-47

6 COMMUNICATIONS

6.5 DNP POINT LISTS

6

6.5.4 ANALOG INPUT / INPUT CHANGE (OBJECTS 30/32)

In the following table, the Format column indicates that the associated data point format is determined by the entry in Table
6–2: Data Formats on page 6–34. For example
, an “F1” format is described in that table as a (16-bit) unsigned value with-
out any decimal places. Therefore, the value read should be interpreted in this manner. Many of the values reported by the
489 have a size of 32-bits and have had their upper and lower 16-bit components assigned to separate points. Where indi-
cated, refer to the appropriate note following the table for more detail.

Table 6–8: ANALOG INPUTS POINT LIST (SHEET 1 OF 4)

INDEX

FORMAT

DESCRIPTION

EVENT CLASS

ASSIGNED TO

NOTES

0

F133

Generator Status

Class 1

Note 3

1

F1

Generator Thermal Capacity Used

Class 1

2

F1

Estimated Trip Time On Overload (seconds, 65535 means never)

Class 1

3

F134

Cause Of Last Trip

Class 1

Note 3

4

F19

Time Of Last Trip (Upper 16 Bits)

Class 1

Notes 3,4

5

F19

Time Of Last Trip (Lower 16 Bits)

Class 1

Notes 3,4

6

F18

Date Of Last Trip (Upper 16 Bits)

Class 1

Notes 3,4

7

F18

Date Of Last Trip (Lower 16 Bits)

Class 1

Notes 3,4

8

F1

Tachometer Pre-Trip

Class 1

Note 3

9

F1

Scale factor for pre-trip current readings (pre-trip points marked with

“Note 6”). Will always be a power of 10 (1, 10, 100, etc.). Changes only

when the configuration setpoints are changed.

Class 1

Note 3

10

F1

Phase A Pre-Trip Current

Class 1

Notes 3, 6

11

F1

Phase B Pre-Trip Current

Class 1

Notes 3, 6

12

F1

Phase C Pre-Trip Current

Class 1

Notes 3, 6

13

F1

Phase A Pre-Trip Differential Current

Class 1

Notes 3, 6

14

F1

Phase B Pre-Trip Differential Current

Class 1

Notes 3, 6

15

F1

Phase C Pre-Trip Differential Current

Class 1

Notes 3, 6

16

F1

Pre-Trip Negative Sequence Current

Class 1

Note 3

17

F1

Ground Current Scale Factor. Will always be a power of 10 (1, 10, 100,

etc.). Changes only when the configuration setpoints are changed.

Class 1

Note 3

18

F6

Pre-Trip Ground Current (scaled according to previous setpoint)

Class 1

Note 3

19

F1

Phase A-B Pre-Trip Voltage

Class 1

Note 3

20

F1

Phase B-C Pre-Trip Voltage

Class 1

Note 3

21

F1

Phase C-A Pre-Trip Voltage

Class 1

Note 3

22

F3

Pre-Trip Frequency

Class 1

Note 3

23

F1

Pre-Trip Real Power (MW)

Class 1

Notes 3,8

24

F1

Pre-Trip Real Power (kW)

Class 1

Notes 3,8

25

F1

Pre-Trip Reactive Power (Mar

Class 1

Notes 3,8

26

F1

Pre-Trip Reactive Power (kvar)

Class 1

Notes 3,8

27

F1

Pre-Trip Apparent Power (MVA)

Class 1

Notes 3,8

28

F1

Pre-Trip Apparent Power (kVA)

Class 1

Notes 3,8

29

F1

Last Trip Stator RTD

Class 1

Note 3

30

F4

Last Trip Hottest Stator RTD Temperature (°C)

Class 1

Note 3

31

F1

Last Trip Bearing RTD

Class 1

Note 3

32

F4

Last Trip Hottest Bearing RTD Temperature (°C)

Class 1

Note 3

33

F1

Last Trip Other RTD

Class 1

Note 3

34

F4

Last Trip Hottest Other RTD Temperature (°C)

Class 1

Note 3

35

F1

Last Trip Ambient RTD

Class 1

Note 3

36

F4

Last Trip Hottest Ambient RTD Temperature (°C)

Class 1

Note 3

37

F12

Pre-Trip Analog Input 1

Class 1

Notes 3,9

Advertising