S2 system setup, 1 current sensing, 2 voltage sensing – GE 489 User Manual

Page 62: 3 s2 system setup, Current sensing -12, Voltage sensing -12

Advertising
background image

4-12

489 Generator Management Relay

GE Multilin

4.3 S2 SYSTEM SETUP

4 SETPOINTS

4

4.3S2 SYSTEM SETUP

4.3.1 CURRENT SENSING

PATH: SETPOINTS

ÖØ

S2 SYSTEM SETUP

Ö

CURRENT SENSING

As a safeguard, the

PHASE CT PRIMARY

and

GENERATOR PARAMETERS

setpoints are defaulted to "--------" when shipped,

indicating that the 489 was never programmed. Once these values are entered, the 489 will be in service. Select the Phase
CT so that the maximum fault current does not exceed 20 times the primary rating. When relaying class CTs are pur-
chased, this precaution helps prevent CT saturation under fault conditions. The secondary value of 1 or 5 A must be spec-
ified when ordering so the proper hardware will be installed. The

PHASE CT PRIMARY

setpoint applies to both the neutral end

CTs as well as the output CTs.

For high resistance grounded systems, sensitive ground current detection is possible if the 50:0.025 Ground CT is used. To
use the 50:0.025 CT input, set

GROUND CT

to "50:0.025". No additional ground CT messages will appear. On solid or low

resistance grounded systems, where fault currents may be quite large, the 489 1 A/5 A secondary Ground CT input should
be used. Select the Ground CT primary so that potential fault current does not exceed 20 times the primary rating. When
relaying class CTs are purchased, this precaution will ensure that the Ground CT does not saturate under fault conditions.

The 489 uses a nominal CT primary rating of 5 A for calculation of pickup levels.

4.3.2 VOLTAGE SENSING

PATH: SETPOINTS

ÖØ

S2 SYSTEM SETUP

ÖØ

VOLTAGE SENSING

The voltage transformer connections and turns ratio are entered here. The VT should be selected such that the secondary
phase-phase voltage of the VTs is between 70.0 and 135.0 V when the primary is at generator rated voltage.

The Neutral VT ratio must be entered here for voltage measurement across the neutral grounding device. Note that the
neutral VT input is not intended to be used at continuous voltages greater than 240 V. If the voltage across the neutral input
is less than 240 V during fault conditions, an auxiliary voltage transformer is not required. If this is not the case, use an aux-
iliary VT to drop the fault voltage below 240 V. The

NEUTRAL VT RATIO

entered must be the total effective ratio of the

grounding transformer and any auxiliary step up or step down VT.

For example, if the distribution transformer ratio is 13200:480 and the auxiliary VT ratio is 600:120, the

NEUTRAL VT RATIO

setpoint is calculated as:

(EQ 4.1)

Therefore, set

NEUTRAL VT RATIO

to 137.50:1

„ CURRENT SENSING
„ [ENTER] for more

PHASE CT PRIMARY:

-------------

Range: 1 to 5000 step 1, Not Programmed

GROUND CT:

50:0.025

Range: None, 1A Secondary, 5A Secondary, 50:0.025

GROUND CT RATIO:

100: 1

Range: 10 to 10000 in steps of 1

Message seen only if Ground CT Type is 1 A

GROUND CT RATIO:

100: 5

Range: 10 to 10000 in steps of 1

Message seen only if Ground CT Type is 5 A

„ VOLTAGE SENSING
„ [ENTER] for more

VT CONNECTION TYPE:

None

Range: Open Delta, Wye, None

VOLTAGE TRANSFORMER

RATIO: 5.00:1

Range: 1.00:1 to 300.00:1 in steps of 0.01

NEUTRAL VOLTAGE

TRANSFORMER: No

Range: No, Yes

NEUTRAL VT

RATIO: 5.00:1

Range: 1.00:1 to 240.00:1 in steps of 0.01. Seen only if

NEUTRAL VOLTAGE TRANSFORMER

is "Yes"

ENTER

ESCAPE

р

р

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

ENTER

ESCAPE

р

р

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

NEUTRAL VT RATIO

Distribution Transformer Ratio Auxiliary VT Ratio

Ч

: 1

=

13200

480

---------------- 600

120

----------

Ч

: 1

137.50 : 1

=

=

Advertising