GE 489 User Manual

Page 194

Advertising
background image

6-32

489 Generator Management Relay

GE Multilin

6.3 MODBUS MEMORY MAP

6 COMMUNICATIONS

6

2D83

FAULT Iphase NEUTRAL

0 to 2000

1

× CT

F3

0

2D84

FAULT CURRENT GROUND

0 to 2000

1

× CT

F3

0

2D85

FAULT VOLTAGE NEUTRAL

0 to 1000

1

Volts

F2

0

2D86

FAULT STATOR RTD TEMP

–50 to 250

1

°C

F4

40

2D87

FAULT BEARING RTD TEMP

–50 to 250

1

°C

F4

40

2D88

FAULT OTHER RTD TEMP

–50 to 250

1

°C

F4

40

2D89

FAULT AMBIENT RTD TEMP

–50 to 250

1

°C

F4

40

2D8A

FAULT SYSTEM FREQUENCY

50 to 900

1

Hz

F2

600

2D8B

FAULT ANALOG INPUT 1

0 to 100

1

%

F1

0

2D8C

FAULT ANALOG INPUT 2

0 to 100

1

%

F1

0

2D8D

FAULT ANALOG INPUT 3

0 to 100

1

%

F1

0

2D8E

FAULT ANALOG INPUT 4

0 to 100

1

%

F1

0

2DBC FAULT STATOR RTD TEMP

–50 to 250

1

°F

F4

40

2DBD FAULT BEARING RTD TEMP

–50 to 250

1

°F

F4

40

2DBE

FAULT OTHER RTD TEMP

–50 to 250

1

°F

F4

40

2DBF

FAULT AMBIENT RTD TEMP

–50 to 250

1

°F

F4

40

489 TESTING / TEST OUTPUT RELAYS

2DE0

FORCE OPERATION OF RELAYS

0 to 8

1

F139

0

489 TESTING / TEST ANALOG OUTPUT

2DF0

FORCE ANALOG OUTPUTS FUNCTION

0 to 1

1

F126

0

2DF1

ANALOG OUTPUT 1 FORCED VALUE

0 to 100

1

%

F1

0

2DF2

ANALOG OUTPUT 2 FORCED VALUE

0 to 100

1

%

F1

0

2DF3

ANALOG OUTPUT 3 FORCED VALUE

0 to 100

1

%

F1

0

2DF4

ANALOG OUTPUT 4 FORCED VALUE

0 to 100

1

%

F1

0

EVENT RECORDER / GENERAL

3000

EVENT RECORDER LAST RESET DATE (2 WORDS)

N/A

N/A

N/A

F18

N/A

3002

TOTAL NUMBER OF EVENTS SINCE LAST CLEAR

0 to 65535

1

N/A

F1

N/A

3003

EVENT RECORD SELECTOR

0 to 65535

1

F1

0

EVENT RECORDER / SELECTED EVENT

3004

CAUSE OF EVENT

0 to 139

1

F134

0

3005

TIME OF EVENT (2 WORDS)

N/A

N/A

N/A

F19

N/A

3007

DATE OF EVENT (2 WORDS)

N/A

N/A

N/A

F18

N/A

3009

TACHOMETER

0 to 7200

1

RPM

F1

0

300A

PHASE A CURRENT

0 to 999999

1

Amps

F12

0

300C

PHASE B CURRENT

0 to 999999

1

Amps

F12

0

300E

PHASE C CURRENT

0 to 999999

1

Amps

F12

0

3010

PHASE A DIFFERENTIAL CURRENT

0 to 999999

1

Amps

F12

0

3012

PHASE B DIFFERENTIAL CURRENT

0 to 999999

1

Amps

F12

0

3014

PHASE C DIFFERENTIAL CURRENT

0 to 999999

1

Amps

F12

0

3016

NEG. SEQ. CURRENT

0 to 2000

1

%FLA

F1

0

3017

GROUND CURRENT

0 to 20000000

1

A

F14

0

3019

A-B VOLTAGE

0 to 50000

1

Volts

F1

0

301A

B-C VOLTAGE

0 to 50000

1

Volts

F1

0

301B

C-A VOLTAGE

0 to 50000

1

Volts

F1

0

301C

FREQUENCY

0 to 12000

1

Hz

F3

0

301D

ACTIVE GROUP

0 to 1

1

F1

0

301F

REAL POWER (MW)

–2000000 to 2000000

1

MW

F13

0

3021

REACTIVE POWER Mar

–2000000 to 2000000

1

Mar

F13

0

3023

APPARENT POWER MVA

0 to 2000000

1

MVA

F13

0

3025

HOTTEST STATOR RTD #

1 to 12

1

F1

1

3026

HOTTEST STATOR RTD TEMPERATURE

–50 to 250

1

°C

F4

0

3027

HOTTEST BEARING RTD #

1 to 12

1

F1

1

3028

HOTTEST BEARING RTD TEMPERATURE

–50 to 250

1

°C

F4

0

3029

HOTTEST OTHER RTD #

1 to 12

1

F1

1

302A

HOTTEST OTHER RTD TEMPERATURE

–50 to 250

1

°C

F4

0

302B

HOTTEST AMBIENT RTD #

1 to 12

1

F1

1

302C

HOTTEST AMBIENT RTD TEMPERATURE

–50 to 250

1

°C

F4

0

302D

ANALOG IN 1

–50000 to 50000

1

Units

F12

0

302F

ANALOG IN 2

–50000 to 50000

1

Units

F12

0

3031

ANALOG IN 3

–50000 to 50000

1

Units

F12

0

3033

ANALOG IN 4

–50000 to 50000

1

Units

F12

0

3035

PHASE A NEUTRAL CURRENT

0 to 999999

1

Amps

F12

0

3037

PHASE B NEUTRAL CURRENT

0 to 999999

1

Amps

F12

0

3039

PHASE C NEUTRAL CURRENT

0 to 999999

1

Amps

F12

0

30E0

HOTTEST STATOR RTD TEMPERATURE

–50 to 250

1

°F

F4

0

30E1

HOTTEST BEARING RTD TEMPERATURE

–50 to 250

1

°F

F4

0

Table 6–1: 489 MEMORY MAP (SHEET 23 OF 24)

ADDR NAME

RANGE

STEP

UNITS

FORMAT

DEFAULT

1, 2, 3

See Table footnotes on page 6–33