GE 489 User Manual

Page 187

Advertising
background image

GE Multilin

489 Generator Management Relay

6-25

6 COMMUNICATIONS

6.3 MODBUS MEMORY MAP

6

POWER ELEMENTS / LOW FORWARD POWER

2280

BLOCK LOW FWD POWER FROM ONLINE

0 to 15000

1

s

F1

0

2281

LOW FORWARD POWER ALARM

0 to 2

1

F115

0

2282

ASSIGN ALARM RELAYS (2-5)

1 to 4

1

F50

16

2283

LOW FWD POWER ALARM LEVEL

2 to 99

1

× Rated MW

F14

5

2285

LOW FWD POWER ALARM DELAY

2 to 1200

1

s

F2

100

2286

LOW FWD POWER ALARM EVENTS

0 to 1

1

F105

0

2287

LOW FORWARD POWER TRIP

0 to 2

1

F115

0

2288

ASSIGN TRIP RELAYS (1-4)

0 to 3

1

F50

1

2289

LOW FWD POWER TRIP LEVEL

2 to 99

1

× Rated MW

F14

5

228B

LOW FWD POWER TRIP DELAY

2 to 1200

1

s

F2

200

RTD TEMPERATURE / RTD TYPES

2400

STATOR RTD TYPE

0 to 3

1

F120

0

2401

BEARING RTD TYPE

0 to 3

1

F120

0

2402

AMBIENT RTD TYPE

0 to 3

1

F120

0

2403

OTHER RTD TYPE

0 to 3

1

F120

0

RTD TEMPERATURE / RTD #1

2420

RTD #1 APPLICATION

0 to 4

1

F121

1

2421

RTD #1 ALARM

0 to 2

1

F115

0

2422

ASSIGN ALARM RELAYS (2-5)

1 to 4

1

F50

16

2423

RTD #1 ALARM TEMPERATURE

1 to 250

1

°C

F1

130

2424

RTD #1 ALARM EVENTS

0 to 1

1

F105

0

2425

RTD #1 TRIP

0 to 2

1

F115

0

2426

RTD #1 TRIP VOTING

1 to 12

1

F122

1

2427

ASSIGN TRIP RELAYS (1-4)

0 to 3

1

F50

1

2428

RTD #1 TRIP TEMPERATURE

1 to 250

1

°C

F1

155

2429

RTD #1 NAME

0 to 8

1

F22

_

RTD TEMPERATURE / RTD #2

2460

RTD #2 APPLICATION

0 to 4

1

F121

1

2461

RTD #2 ALARM

0 to 2

1

F115

0

2462

ASSIGN ALARM RELAYS (2-5)

1 to 4

1

F50

16

2463

RTD #2 ALARM TEMPERATURE

1 to 250

1

°C

F1

130

2464

RTD #2 ALARM EVENTS

0 to 1

1

F105

0

2465

RTD #2 TRIP

0 to 2

1

F115

0

2466

RTD #2 TRIP VOTING

1 to 12

1

F122

2

2467

ASSIGN TRIP RELAYS (1-4)

0 to 3

1

F50

1

2468

RTD #2 TRIP TEMPERATURE

1 to 250

1

°C

F1

155

2469

RTD #2 NAME

0 to 8

1

F22

_

RTD TEMPERATURE / RTD #3

24A0

RTD #3 APPLICATION

0 to 4

1

F121

1

24A1

RTD #3 ALARM

0 to 2

1

F115

0

24A2

ASSIGN ALARM RELAYS (2-5)

1 to 4

1

F50

16

24A3

RTD #3 ALARM TEMPERATURE

1 to 250

1

°C

F1

130

24A4

RTD #3 ALARM EVENTS

0 to 1

1

F105

0

24A5

RTD #3 TRIP

0 to 2

1

F115

0

24A6

RTD #3 TRIP VOTING

1 to 12

1

F122

3

24A7

ASSIGN TRIP RELAYS (1-4)

0 to 3

1

F50

1

24A8

RTD #3 TRIP TEMPERATURE

1 to 250

1

°C

F1

155

24A9

RTD #3 NAME

0 to 8

1

F22

_

RTD TEMPERATURE / RTD #4

24E0

RTD #4 APPLICATION

0 to 4

1

F121

1

24E1

RTD #4 ALARM

0 to 2

1

F115

0

24E2

ASSIGN ALARM RELAYS (2-5)

1 to 4

1

F50

16

24E3

RTD #4 ALARM TEMPERATURE

1 to 250

1

°C

F1

130

24E4

RTD #4 ALARM EVENTS

0 to 1

1

F105

0

24E5

RTD #4 TRIP

0 to 2

1

F115

0

24E6

RTD #4 TRIP VOTING

1 to 12

1

F122

4

24E7

ASSIGN TRIP RELAYS (1-4)

0 to 3

1

F50

1

24E8

RTD #4 TRIP TEMPERATURE

1 to 250

1

°C

F1

155

24E9

RTD #4 NAME

0 to 8

1

F22

_

RTD TEMPERATURE / RTD #5

2520

RTD #5 APPLICATION

0 to 4

1

F121

1

2521

RTD #5 ALARM

0 to 2

1

F115

0

2522

ASSIGN ALARM RELAYS (2-5)

1 to 4

1

F50

16

2523

RTD #5 ALARM TEMPERATURE

1 to 250

1

°C

F1

130

2524

RTD #5 ALARM EVENTS

0 to 1

1

F105

0

Table 6–1: 489 MEMORY MAP (SHEET 16 OF 24)

ADDR NAME

RANGE

STEP

UNITS

FORMAT

DEFAULT

1, 2, 3

See Table footnotes on page 6–33