4 voltage phase reversal accuracy, 5 injection test setup #2, Voltage phase reversal accuracy -12 – GE 489 User Manual

Page 224: Injection test setup #2 -12

Advertising
background image

7-12

489 Generator Management Relay

GE Multilin

7.3 ADDITIONAL FUNCTIONAL TESTS

7 TESTING

7

7.3.4 VOLTAGE PHASE REVERSAL ACCURACY

The can detect voltage phase rotation and protect against phase reversal. To test the phase reversal element, perform the
following steps:

1.

Alter the following setpoints:

S2 SYSTEM SETUP

ÖØ

VOLTAGE SENSING

Ö

VT CONNECTION TYPE:

"Wye"

S2 SYSTEM SETUP

ÖØ

GEN. PARAMETERS

ÖØ

GENERATOR PHASE SEQUENCE:

"ABC"

S3 DIGITAL INPUTS

Ö

BREAKER STATUS

Ö

BREAKER STATUS:

"Breaker Auxiliary a"

S6 VOLTAGE ELEMENTS

ÖØ

PHASE REVERSAL

Ö

PHASE REVERSAL TRIP:

"Unlatched"

S6 VOLTAGE ELEMENTS

ÖØ

PHASE REVERSAL

ÖØ

ASSIGN TRIP RELAYS:

"1---"

2.

Apply voltages as per the table below. Verify the operation on voltage phase reversal

7.3.5 INJECTION TEST SETUP #2

Setup the 489 device as follows for the GE Multilin HGF Ground Accuracy Test, Neutral Voltage (3rd Harmonic) Accuracy
Test, and the Phase Differential Trip Test.

Figure 7–2: SECONDARY INJECTION SETUP #2

APPLIED VOLTAGE

EXPECTED RESULT

OBSERVED RESULT

Va = 120 V

∠0°

Vb = 120 V

∠120° lag

Vc = 120 V

∠240° lag

NO TRIP

Va = 120 V

∠0°

Vb = 120 V

∠240° lag

Vc = 120 V

∠120° lag

PHASE REVERSAL TRIP

E10

V

NE

UT

R

AL

1

A

H

G

F

1

A

/5A

1

A

/5A

1

A

/5A

1

A

/5A

1

A

/5A

1

A

/5A

C

OM

C

OM

C

OM

C

OM

C

OM

PHASE a PHASE b PHASE c

PHASE A PHASE B PHASE C

C

OM

C

OM

C

OM

V

a

V

b

V

com

V

c

H9

G3

G6

H4

H7

H1

F10

A

B

C

N

A

B

C

N

V V V V

I

I

I

I

3 PHASE VARIABLE AC TEST SET

GROUND INPUTS

NEUTRAL END CT's

OUTPUT CT's

PHASE

VOLTAGE INPUTS

G10

H3

H6

G5

G8

H2

808817A1.CDR

G9

50:0.25

NC

NC

H10

G4

G7

G2

H5

H8

G1

AUTOMATIC CT

SHORTING

BAR

VC

VA

VB

Advertising