489 Generator Management Relay

7-15

7 TESTING

7.3 ADDITIONAL FUNCTIONAL TESTS

7

f) TEST RESULTS

7.3.9 INJECTION TEST SETUP #3

Setup the 489 device as follows for the Voltage Restrained Overcurrent test.

Figure 7–3: SECONDARY INJECTION TEST SETUP #3

TEST

PHASE A

PHASE B

PHASE C

CALCULATED

MEASURED

CALCULATED

MEASURED

CALCULATED

MEASURED

Minimum Pickup

TEST

PHASE A

PHASE B

PHASE C

CT

5

× CT

CT

5

× CT

CT

5

× CT

Single Infeed Fault

TEST

PHASE A

PHASE B

PHASE C

OPERATE

RESTRAIN

OPERATE

RESTRAIN

OPERATE

RESTRAIN

Slope 1

I

x

I

y

Operation

(OK/not OK)

Slope 2

I

x

I

y

Operation

(OK/not OK)

Directional

Check

I

x

N/A

N/A

N/A

I

y

N/A

N/A

N/A

Operation

(OK/not OK)

N/A

N/A

N/A

E10

V

NE

UT

R

AL

1

A

H

G

F

1

A

/5A

1

A

/5A

1

A

/5A

1

A

/5A

1

A

/5A

1

A

/5A

C

OM

C

OM

C

OM

C

OM

C

OM

PHASE a PHASE b PHASE c

PHASE A PHASE B PHASE C

C

OM

C

OM

C

OM

V

a

V

b

V

com

V

c

H9

G3

G6

H4

H7

H1

F10

A

B

C

N

A

B

C

N

V V V V

I

I

I

I

3 PHASE VARIABLE AC TEST SET

GROUND INPUTS

NEUTRAL END CT's

OUTPUT CT's

808822A2.CDR

PHASE

VOLTAGE INPUTS

G10

H3

H6

G5

G8

H2

G9

H10

G4

G7

G2

H5

H8

G1

AUTOMATIC CT

SHORTING

BAR

VC

VA

VB