489 Generator Management Relay

GE Multilin

5.2 A1 STATUS

5 ACTUAL VALUES

5

Any active or latched alarms may be viewed here.

5.2.4 TRIP PICKUPS

PATH: ACTUAL VALUES

Ö

A1 STATUS

ÖØ

TRIP PICKUPS

THERMAL MODEL

ALARM: 100% TC USED

Range: 1 to 100%

The thermal capacity used is shown here.

TRIP COUNTER

ALARM: 25 Trips

Range: 1 to 10000

The number of generator trips is shown here.

BREAKER FAILURE

ALARM: Active

Range: Active, Latched. Active if condition that caused

the alarm is still present.

TRIP COIL MONITOR

ALARM: Active

Range: Active, Latched. Active if condition that caused

the alarm is still present.

VT FUSE FAILURE

ALARM: Active

Range: Active, Latched. Active if condition that caused

the alarm is still present.

CURRENT DEMAND

ALARM: 1053 A

Range: 1 to 999999 A.

The running current demand is shown here.

MW DEMAND

ALARM: 50.500

Range: –2000.000 to +2000.000 MW

Current Running MW Demand is shown here

Mvar DEMAND

ALARM: –20.000

Range: –2000.000 to +2000.000 Mvar

Current Running Mvar Demand is shown here

MVA DEMAND

ALARM: 20.000

Range: 0 to 2000.000 MVA

Current Running MVA Demand is shown here

GEN. RUNNING HOURS

ALARM: 1000 h

Range: 0 to 1000000 hrs. Seen only if the Running

Hour Alarm is enabled.

ANALOG I/P 1

ALARM: 201 Units

Range: –50000 to +50000. Reflects the Analog Input 1

Name. The Analog Input level is shown here.

ANALOG I/P 2

ALARM: 201 Units

Range: –50000 to +50000. Reflects the Analog Input 2

Name. The Analog Input level is shown here.

ANALOG I/P 3

ALARM: 201 Units

Range: –50000 to +50000. Reflects the Analog Input 3

Name. The Analog Input level is shown here.

ANALOG I/P 4

ALARM: 201 Units

Range: –50000 to +50000. Reflects the Analog Input 4

Name. The Analog Input level is shown here.

ALARM, 489 NOT

INSERTED PROPERLY

If the 489 chassis is only partially engaged with the

case, this service alarm appears after 1 sec.
Secure the chassis handle to ensure that all
contacts mate properly

489 NOT IN SERVICE

Simulation Mode

Range: Not Programmed, Simulation Mode, Output

Relays Forced, Analog Output Forced, Test
Switch Shorted

IRIG-B FAILURE

ALARM: Active

Range: Active. Seen only if IRIG-B is enabled and the

associated signal input is lost.

„ TRIP PICKUPS
„ [ENTER] for more

Input A

PICKUP: Not Enabled

Range: Not Enabled, Inactive, Timing Out, Active Trip,

Latched Trip. Reflects Input Name as
programmed. Seen only if function assigned is
an input.

Input B

PICKUP: Not Enabled

Range: see Input A PICKUP above

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

ENTER

ESCAPE

р

р

MESSAGE

ESCAPE

Advertising