489 Generator Management Relay

GE Multilin

4.8 S7 POWER ELEMENTS

4 SETPOINTS

4

4.8.2 REACTIVE POWER

PATH: SETPOINTS

ÖØ

S7 POWER ELEMENTS

Ö

REACTIVE POWER

In a motor/generator application, it may be desirable not to trip or alarm on reactive power until the machine is online and
the field has been applied. Therefore, this feature can be blocked until the machine is online and adequate time has expired
during which the field had been applied. From that point forward, the reactive power trip and alarm elements will be active.
A value of zero for the block time indicates that the reactive power protection is active as soon as both current and voltage
are measured regardless of whether the generator is online or offline. Once the 3-phase total reactive power exceeds the
positive or negative level, for the specified delay, a trip or alarm will occur indicating a positive or negative Mvar condition.
The level is programmed in per unit of generator rated Mvar calculated from the rated MVA and rated power factor. The
reactive power elements can be used to detect loss of excitation. If the VT type is selected as "None" or VT fuse loss is
detected, the reactive power protection is disabled. Rated Mvars for the system can be calculated as follows:

For example, given Rated MVA = 100 MVA and Rated Power Factor = 0.85, we have

(EQ 4.25)

„ REACTIVE POWER
„ [ENTER] for more

BLOCK Mvar ELEMENT

FROM START: 1 s

Range: 0 to 5000 s in steps of 1

REACTIVE POWER

ALARM: Off

Range: Off, Latched, Unlatched

ASSIGN ALARM

RELAYS (2-5): ---5

Range: Any combination of Relays 2 to 5

POSITIVE Mvar ALARM

LEVEL: 0.85 x Rated

Range: 0.02 to 2.01

× Rated in steps of 0.01

NEGATIVE Mvar ALARM

LEVEL: 0.85 x Rated

Range: 0.02 to 2.01

× Rated in steps of 0.01

POSITIVE Mvar ALARM

DELAY: 10.0 s

Range: 0.2 to 120.0 s in steps of 0.1

Note: Lagging vars, overexcited

NEGATIVE Mvar ALARM

DELAY: 1.0 s

Range: 0.2 to 120.0 s in steps of 0.1

Note: Leading vars, underexcited

REACTIVE POWER ALARM

EVENTS: Off

Range: On, Off

REACTIVE POWER

TRIP: Off

Range: Off, Latched, Unlatched

ASSIGN TRIP

RELAYS (1-4): 1---

Range: Any combination of Relays 1 to 4

POSITIVE Mvar TRIP

LEVEL: 0.80 x Rated

Range: 0.02 to 2.01

× Rated in steps of 0.01

NEGATIVE Mvar TRIP

LEVEL: 0.80 x Rated

Range: 0.02 to 2.01

× Rated in steps of 0.01

POSITIVE Mvar TRIP

DELAY: 20.0 s

Range: 0.2 to 120.0 s in steps of 0.1

Note: Lagging vars, overexcited

NEGATIVE Mvar TRIP

DELAY: 20.0 s

Range: 0.2 to 120.0 s in steps of 0.1

Note: Leading vars, underexcited

ENTER

ESCAPE

р

р

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

Rated Mvars

Rated MVA

cos

1

Rated PF

(

)

(

)

sin

×

100

cos

1

0.85

(

)

(

)

sin

×

52.67 Mvars

=

=

=