5-14

489 Generator Management Relay

GE Multilin

5.3 A2 METERING DATA

5 ACTUAL VALUES

5

5.3.2 VOLTAGE METERING

PATH: ACTUAL VALUES

ÖØ

A2 METERING DATA

ÖØ

VOLTAGE METERING

Measured voltage parameters will be displayed here. The V/Hz measurement is a per unit value based on Vab voltage/
measured frequency divided by VT nominal/nominal system frequency. Polar coordinates for measured phase and/or line
voltages are also shown using Va (wye connection) or Vab (open delta connection) as a zero angle reference vector. In the
absence of a voltage signal (Va or Vab), IA output current is used as the zero angle reference vector.

If

VT CONNECTION TYPE

is programmed as "None" and

NEUTRAL VOLTAGE TRANSFORMER

is "No" in S2 SYSTEM, the follow-

ing flash message will appear when an attempt is made to enter this group of messages.

„ VOLTAGE METERING
„ [ENTER] for more

Vab:

0

Vbc:

0

Vca:

0

Volts

Range: 0 to 50000 V. Not seen if VT CONNECTION is

programmed as None.

AVERAGE LINE

VOLTAGE: 0 Volts

Range: 0 to 50000 V. Not seen if VT CONNECTION is

programmed as None.

Van:

0

Vbn:

0

Vcn:

0

Volts

Range: 0 to 50000 V. Seen only if VT CONNECTION is

programmed as Wye.

AVERAGE PHASE

VOLTAGE: 0 Volts

Range: 0 to 50000 V. Seen only if VT CONNECTION is

programmed as Wye.

LINE A-B VOLTAGE:

0 V

0° Lag

Range: 0 to 50000 V, 0 to 359°. Not seen if VT

CONNECTION is programmed as None.

LINE B-C VOLTAGE:

0 V

0° Lag

Range: 0 to 50000 V, 0 to 359°. Not seen if VT

CONNECTION is programmed as None.

LINE C-A VOLTAGE:

0 V

0° Lag

Range: 0 to 50000 V, 0 to 359°. Not seen if VT

CONNECTION is programmed as None.

PHASE A-N VOLTAGE:

0 V

0° Lag

Range: 0 to 50000 V, 0 to 359°. Seen only if VT

CONNECTION is programmed as Wye.

PHASE B-N VOLTAGE:

0 V

0° Lag

Range: 0 to 50000 V, 0 to 359°. Seen only if VT

CONNECTION is programmed as Wye.

PHASE C-N VOLTAGE:

0 V

0° Lag

Range: 0 to 50000 V, 0 to 359°. Seen only if VT

CONNECTION is programmed as Wye.

PER UNIT MEASUREMENT

OF V/Hz: 0.00

Range: 0.00 to 2.00. Not seen if VT CONNECTION is

programmed as None.

FREQUENCY:

0.00 Hz

Range: 0.00 to 90.00 Hz. Not seen if VT CONNECTION

is programmed as None.

NEUTRAL VOLTAGE

FUND: 0.0 V

Range: 0.0 to 25000.0 V. Seen only if there is a neutral

voltage transformer.

NEUTRAL VOLTAGE

3rd HARM: 0.0 V

Range: 0.0 to 25000.0 V. Seen only if there is a neutral

voltage transformer.

TERMINAL VOLTAGE

3rd HARM: 0.0 V

Range: 0.0 to 25000.0 V. Seen only if VT CONNECTION

is programmed as Wye.

IMPEDANCE Vab / Iab

0.0

Ω sec.

Range: 0.0 to 6553.5

Ωsec., 0 to 359°

THIS FEATURE

NOT PROGRAMMED

ENTER

ESCAPE

р

р

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

Advertising