GE Multilin

489 Generator Management Relay

4-51

4 SETPOINTS

4.9 S8 RTD TEMPERATURE

4

4.9.3 RTDS 7 TO 10

PATH: SETPOINTS

ÖØ

S8 RTD TEMPERATURE

ÖØ

RTD #7(10)

RTDs 7 through 10 default to Bearing RTD type. There are individual alarm and trip configurations for each RTD. This
allows one of the RTDs to be turned off if it malfunctions. The alarm level and the trip level are normally set slightly above
the normal running temperature, but below the bearing temperature rating. Trip voting has been added for extra reliability in
the event of RTD malfunction. If enabled, a second RTD must also exceed the trip temperature of the RTD being checked
before a trip will be issued. If the RTD is chosen to vote with itself, the voting feature is disabled. Each RTD name may be
changed if desired.

„ RTD #7
„ [ENTER] for more

RTD #7 APPLICATION:

Bearing

Range: Stator, Bearing, Ambient, Other, None

RTD #7 NAME:

Range: 8 alphanumeric characters

RTD #7 ALARM:

Off

Range: Off, Latched, Unlatched

ASSIGN ALARM

RELAYS (2-5): ---5

Range: Any combination of Relays 2 to 5.

RTD #7 ALARM

TEMPERATURE: 80°C

Range: 1 to 250°C in steps of 1

RTD #7 ALARM

EVENTS: Off

Range: On, Off

RTD #7 TRIP:

Off

Range: Off, Latched, Unlatched

RTD #7 TRIP VOTING:

RTD #7

Range: RTD #1 to RTD #12

ASSIGN TRIP

RELAYS (1-4): 1---

Range: Any combination of Relays 1 to 4

RTD #7 TRIP

TEMPERATURE: 90°C

Range: 1 to 250°C in steps of 1