4.7 S6 VOLTAGE ELEMENTS

4 SETPOINTS

4

4.7.2 OVERVOLTAGE

PATH: SETPOINTS

ÖØ

S6 VOLTAGE ELEMENTS

ÖØ

OVERVOLTAGE

The overvoltage elements may be used for protection of the generator and/or its auxiliary equipment during prolonged
overvoltage conditions. They are always active (when the generator is offline or online). The alarm element is definite time
and the trip element can be either definite time or an inverse time curve. When the average of the measured phase-phase
voltages rises above the pickup level x the generator rated phase-phase voltage, the element will begin to time out. If the
time expires, a trip or alarm will occur. The reset rate is a linear reset time from the threshold of trip. The pickup levels are
insensitive to frequency over the range of 5 to 90 Hz.

„ OVERVOLTAGE
„ [ENTER] for more

OVERVOLTAGE

ALARM: Off

Range: Off, Latched, Unlatched

ASSIGN ALARM

RELAYS (2-5): ---5

Range: Any combination of Relays 2 to 5

OVERVOLTAGE ALARM

PICKUP: 1.15 x Rated

Range: 1.01 to 1.50

× Rated in steps of 0.01

OVERVOLTAGE ALARM

DELAY: 3.0 s

Range: 0.2 to 120.0 s in steps of 0.1

OVERVOLTAGE ALARM

EVENTS: Off

Range: On, Off

OVERVOLTAGE

TRIP: Off

Range: Off, Latched, Unlatched

ASSIGN TRIP

RELAYS (1-4): 1---

Range: Any combination of Relays 1 to 4

OVERVOLTAGE TRIP

PICKUP: 1.20 x Rated

Range: 1.01 to 1.50

× Rated in steps of 0.01

OVERVOLTAGE TRIP

DELAY: 1.0 s

Range: 0.1 to 10.0 s in steps of 0.1

OVERVOLTAGE CURVE

RESET RATE: 1.4 s

Range: 0.0 to 999.9 s in steps of 0.1

OVERVOLTAGE CURVE

ELEMENT: Curve

Range: Curve, Definite Time

The formula for the curve is:

(EQ 4.19)

where: T = trip time in seconds

D =

OVERVOLTAGE TRIP DELAY

setpoint

V = actual average phase-phase voltage
V

pickup

=

OVERVOLTAGE TRIP PICKUP

setpoint

ENTER

ESCAPE

р

р

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

T

D

V V

pickup

(

) 1

-----------------------------------------

=

, when V V

pickup

>

808741A1.CDR

0.1

1

10

100

1000

1

1.1

1.2

1.3

1.4

1.5

1.6

1.7

1.8

1.9

2

Multiples of Overvoltage Pickup

10

3

1

0.3

0.1

T

im

et

oT

ri

p

(s

e

c

ond

s)

T

IM

E

D

E

LA

Y

S

E

TT

IN

G