6 pulse output, 7 generator running hour setup – GE 489 User Manual

Page 124

Advertising
background image

4-74

489 Generator Management Relay

GE Multilin

4.11 S10 MONITORING

4 SETPOINTS

4

4.11.6 PULSE OUTPUT

PATH: SETPOINTS

ÖØ

S10 MONITORING

ÖØ

PULSE OUTPUT

The 489 can perform pulsed output of positive kWh and both positive and negative kvarh. Each output parameter can be
assigned to any one of the alarm or auxiliary relays. Pulsed output is disabled for a parameter if the relay setpoint is
selected as OFF for that pulsed output. The minimum time between pulses is fixed to 400 milliseconds.

This feature should be programmed so that no more than one pulse per 600 milliseconds is required or the pulsing
will lag behind the interval activation. Do not assign pulsed outputs to the same relays as alarms and trip functions.

Figure 4–22: PULSE OUTPUT

4.11.7 GENERATOR RUNNING HOUR SETUP

PATH: SETPOINTS

ÖØ

S10 MONITORING

ÖØ

RUNNING HORU SETUP

The 489 can measure the generator running hours. This value may be of interest for periodic maintenance of the generator.
The initial generator running hour allows the user to program existing accumulated running hours on a particular generator
the relay is protecting. This feature switching 489 relays without losing previous generator running hour values.

„ PULSE OUTPUT
„ [ENTER] for more

POS. kWh PULSE OUT

RELAYS (2-5): ----

Range: Any combination of Relays 2 to 5

POS. kWh PULSE OUT

INTERVAL: 10 kWh

Range: 1 to 50000 kWh in steps of 1

POS. kvarh PULSE OUT

RELAYS (2-5): ----

Range: Any combination of Relays 2 to 5

POS. kvarh PULSE OUT

INTERVAL: 10 kvarh

Range: 1 to 50000 kvarh in steps of 1

NEG. kvarh PULSE OUT

RELAYS (2-5): ----

Range: Any combination of Relays 2 to 5

NEG. kvarh PULSE OUT

INTERVAL: 10 kvarh

Range: 1 to 50000 kvarh in steps of 1

PULSE WIDTH:

200 ms

Range: 200 to 1000 ms in steps of 1

„ RUNNING HOUR SETUP
„ [ENTER] for more

INITIAL GEN. RUNNING

HOURS: 0 h

Range: 0 to 999999 h in steps of 1

GEN. RUNNING HOURS

ALARM: Off

Range: Off, Latched, Unlatched

ASSIGN ALARM

RELAYS (2-5): ---5

Range: Any combination of Relays 2 to 5

GEN. RUNNING HOURS

LIMIT: 1000 h

Range: 1 to 1000000 h in steps of 1

ENTER

ESCAPE

р

р

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

NOTE

808738A1.CDR

PULSE
WIDTH

normally open (NO) contact

normally closed (NC) contact

status

OPEN

CLOSED

status

CLOSED

OPEN

status

OPEN

CLOSED

ENTER

ESCAPE

р

р

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE