9 output relays, Output relays -8 – GE 489 User Manual

Page 220

Advertising
background image

7-8

489 Generator Management Relay

GE Multilin

7.2 HARDWARE FUNCTIONAL TESTS

7 TESTING

7

0 to 1 mA ANALOG INPUTS:

1.

Alter the following setpoints:

S11 ANALOG I/O

ÖØ

ANALOG INPUT1

Ö

ANALOG INPUT1:

"0-1 mA"

S11 ANALOG I/O

ÖØ

ANALOG INPUT1

ÖØ

ANALOG INPUT1 MINIMUM:

"0"

S11 ANALOG I/O

ÖØ

ANALOG INPUT1

ÖØ

ANALOG INPUT1 MAXIMUM:

"1000" (repeat for Analog Inputs 2 to 4)

2.

Analog output values should be

±0.01 mA on the ammeter. Measured analog input values should be ±10 units. Force

the analog outputs using the following setpoints:

S12 TESTING

ÖØ

TEST ANALOG OUTPUT

Ö

FORCE ANALOG OUTPUTS FUNCTION: "

Enabled"

S12 TESTING

ÖØ

TEST ANALOG OUTPUT

ÖØ

ANALOG OUTPUT 1 FORCED VALUE:

"0%" (enter %, repeat for Outputs 2 to 4)

Verify the ammeter readings as well as the measured analog input readings. View the measured values in:

A2 METERING DATA

ÖØ

ANALOG INPUTS

7.2.9 OUTPUT RELAYS

To verify the functionality of the output relays, perform the following steps:

1.

Using the setpoint:

S12 TESTING

ÖØ

TEST OUTPUT RELAYS

ÖØ

FORCE OPERATION OF RELAYS:

"R1 Trip"

select and store values as per the table below, verifying operation

The R6 Service relay is failsafe or energized normally. Operating R6 causes it to de-energize.

ANALOG

OUTPUT

FORCE

VALUE

EXPECTED

AMMETER

READING

MEASURED AMMETER READING

(MA)

EXPECTED

ANALOG INPUT

READING

MEASURED ANALOG INPUT

READING (UNITS)

1

2

3

4

1

2

3

4

0%

0 mA

0 units

25%

0.25 mA

250 units

50%

0.50 mA

500 units

75%

0.75 mA

750 units

100%

1.00 mA

1000 units

FORCE

OPERATION

SETPOINT

EXPECTED MEASUREMENT

( FOR SHORT)

ACTUAL MEASUREMENT

( FOR SHORT)

R1

R2

R3

R4

R5

R6

R1

R2

R3

R4

R5

R6

NO NC NO NC NO NC NO NC NO NC NO NC NO NC NO NC NO NC NO NC NO NC NO NC

R1 Trip
R2 Auxiliary
R3 Auxiliary
R4 Auxiliary
R5 Alarm
R6 Service
All Relays
No Relays

NOTE

Advertising