A.1.4 – GE 489 User Manual

Page 231

Advertising
background image

GE Multilin

489 Generator Management Relay

A-3

APPENDIX A

A.1 STATOR GROUND FAULT

A

Again the time delay on this element must be coordinated with protection elements downstream, if the generator is
grounded. Refer to Section 4.6.7: Ground Overcurrent on page 4–29 for the range of settings of the pickup levels and the
time delays. The time delay on this element should always be longer than the longest delay on line protection downstream.

Figure A–3: GROUND OVERCURRENT ELEMENT WITH DIFFERENT CURRENT SOURCE SIGNALS

A.1.4 GROUND DIRECTIONAL ELEMENT

The 489 can detect internal stator ground faults using a Ground Directional element implemented using the V

neutral

and the

ground current inputs. The voltage signal is obtained across the grounding impedance of the generator. The ground, or
zero sequence, current is obtained from a core balance CT, as shown below (due to CT inaccuracies, it is generally not
possible to sum the outputs of the conventional phase CTs to derive the generator high-side zero sequence current, for an
impedance-grounded generator).

If correct polarities are observed in the connection of all signals to the relay, the V

neutral

signal will be in phase with the

ground current signal. The element has been provided with a setting allowing the user to change the plane of operation to
cater to reactive grounding impedances or to polarity inversions.

This element’s normal "plane of operation" for a resistor-grounded generator is the 180° plane, as shown in Figure A–4:
Ground Directional Element Polarities and Plane of Operation, fo
r an internal ground fault. That is, for an internal stator-to-
ground fault, the V

o

signal is 180° away from the I

o

signal, if the polarity convention is observed. If the grounding imped-

ance is inductive, the plane of operation will be the 270° plane, again, with the polarity convention shown below. If the polar-
ity convention is reversed on one input, the user will need to change the plane of operation by 180°.

Figure A–4: GROUND DIRECTIONAL ELEMENT POLARITIES AND PLANE OF OPERATION

808736A1.CDR

489

GENERATOR

CORE

BALANCE

CT

CORE

BALANCE

CT

Phase CTs

BREAKER

Breaker
Aux.

Option 2

Option 1

Option 5

(similar to

Option 4)

Option 3

Option 4

Ground

Overcurrent

Element

Ground current input

from one of the five

options

808735A1.CDR

GENERATOR

I

o

CORE

BALANCE

CT

Plane of operation

for resistive

grounding impedance

180°

270°

90°

Grounding

Resistor

Isolating
Transformer

489

Relay

V

o

F10

E10

H10

G10

I

o

I

o

I

o

±

±

Advertising