4 SETPOINTS

4.4 S3 DIGITAL INPUTS

4

4.4.3 GENERAL INPUT A TO G

PATH: SETPOINTS

ÖØ

S3 DIGITAL INPUTS

ÖØ

GENERAL INPUT A(G)

The seven General Input functions are flexible enough to meet most of the desired digital input requirements. The asserted
state and the name of the digital inputs are programmable. To disable the input functions when the generator is offline, until
some time after the generator is brought online, a block time should be set. The input functions will be enabled once the
block delay has expired. A value of zero for the block time indicates that the input functions are always enabled.

Inputs may be configured for control, alarm, or trip. If the control feature is enabled, the assigned output relay(s) operate
when the input is asserted. If the

PULSED CONTROL RELAY DWELL TIME

is set to 0, the output relay(s) operate only while the

input is asserted. However, if a dwell time is assigned, the output relay(s) operate as soon as the input is asserted for a
period of time specified by the setpoint. If an alarm or trip is enabled and the input is asserted, an alarm or trip will occur
after the specified delay.

„ GENERAL INPUT A
„ [ENTER] for more

ASSIGN DIGITAL

INPUT: None

Range: None, Input 1 to Input 7. If an input is assigned to

the Tachometer function, it may not be used here

ASSERTED DIGITAL

INPUT STATE: Closed

Range: Closed, Open

INPUT NAME:

Input A

Range: 12 alphanumeric characters

BLOCK INPUT

FROM ONLINE: 0 s

Range: 0 to 5000 in steps of 1. "0" indicates feature is

active while generator is offline as well as online.

GENERAL INPUT A

CONTROL: Off

Range: Off, On

PULSED CONTROL RELAY

DWELL TIME: 0.0 s

Range: 0.0 to 25.0 s in steps of 0.1

ASSIGN CONTROL

RELAYS (1-5): -----

Range: Any combination of Relays 1 to 5

GENERAL INPUT A

CONTROL EVENTS: Off

Range: Off, On

GENERAL INPUT A

ALARM: Off

Range: Off, Latched, Unlatched

ASSIGN ALARM

RELAYS (2-5): ---5

Range: Any combination of Relays 2 to 5

GENERAL INPUT A

ALARM DELAY: 0.5 s

Range: 0.1 to 5000.0 s in steps of 0.1

GENERAL INPUT A

ALARM EVENTS: Off

Range: Off, On

GENERAL INPUT A

TRIP: Off

Range: Off, Latched, Unlatched

ASSIGN TRIP

RELAYS (1-4): 1---

Range: Any combination of Relays 1 to 4

GENERAL INPUT A

TRIP DELAY: 5.0 s

Range: 0.1 to 5000.0 in steps of 0.1

ENTER

ESCAPE

р

р

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

Advertising