GE 489 User Manual

Page 186

Advertising
background image

6-24

489 Generator Management Relay

GE Multilin

6.3 MODBUS MEMORY MAP

6 COMMUNICATIONS

6

VOLTAGE ELEMENTS / NEUTRAL U/V (3rd)

20E0

LOW POWER BLOCKING LEVEL

2 to 99

1

× Rated MW

F14

5

20E2

LOW VOLTAGE BLOCKING LEVEL

50 to 100

1

× Rated

F3

75

20E3

NEUTRAL UNDERVOLTAGE ALARM

0 to 2

1

F115

0

20E4

ASSIGN ALARM RELAYS (2-5)

1 to 4

1

F50

16

20E5

NEUTRAL U/V ALARM LEVEL

5 to 200

1

V

F2

5

20E6

NEUTRAL UNDERVOLTAGE ALARM DELAY

5 to 120

1

s

F1

30

20E7

NEUTRAL UNDERVOLTAGE ALARM EVENTS

0 to 1

1

F105

0

20E8

NEUTRAL UNDERVOLTAGE TRIP

0 to 2

1

F115

0

20E9

ASSIGN TRIP RELAYS (1-4)

0 to 3

1

F50

1

20EA

NEUTRAL U/V TRIP LEVEL

5 to 200

1

V

F2

10

20EB

NEUTRAL UNDERVOLTAGE TRIP DELAY

5 to 120

1

s

F1

30

VOLTAGE ELEMENTS / LOSS OF EXCITATION

2100

ENABLE VOLTAGE SUPERVISION

0 to 1

1

F103

0

2101

VOLTAGE LEVEL

70 to 100

1

× rated

F3

70

2102

CIRCLE 1 TRIP

0 to 2

1

F115

0

2103

ASSIGN CIRCLE 1 TRIP RELAYS (1-4)

0 to 3

1

F50

1

2104

CIRCLE 1 DIAMETER

25 to 3000

1

Ω s

F2

250

2105

CIRCLE 1 OFFSET

10 to 3000

1

Ω s

F2

25

2106

CIRCLE 1 TRIP DELAY

1 to 100

1

s

F2

50

2107

CIRCLE 2 TRIP

0 to 2

1

F115

0

2108

ASSIGN CIRCLE 2 TRIP RELAYS (1-4)

0 to 3

1

F50

1

2109

CIRCLE 2 DIAMETER

25 to 3000

1

Ω s

F2

350

210A

CIRCLE 2 OFFSET

10 to 3000

1

Ω s

F2

25

210B

CIRCLE 2 TRIP DELAY

1 to 100

1

s

F2

50

VOLTAGE ELEMENTS / DISTANCE ELEMENT

2130

STEP UP TRANSFORMER SETUP

0 to 1

1

F219

0

2131

FUSE FAILURE SUPERVISION

0 to 1

1

F105

0

2132

ZONE 1 TRIP

0 to 2

1

F115

0

2133

ASSIGN ZONE 1 TRIP RELAYS (1-4)

0 to 3

1

F50

1

2134

ZONE 1 REACH

1 to 5000

1

Ω s

F2

100

2135

ZONE 1 ANGLE

50 to 85

1

°

F1

75

2136

ZONE 1 TRIP DELAY

0 to 1500

1

s

F2

4

2137

ZONE 2 TRIP

0 to 2

1

F115

0

2138

ASSIGN ZONE 2 TRIP RELAYS (1-4)

0 to 3

1

F50

1

2139

ZONE 2 REACH

1 to 5000

1

Ω s

F2

100

213A

ZONE 2 ANGLE

50 to 85

1

°

F1

75

213B

ZONE 2 TRIP DELAY

0 to 1500

1

s

F2

20

POWER ELEMENTS / REACTIVE POWER

2200

BLOCK Mvar ELEMENT FROM ONLINE

0 to 5000

1

s

F1

1

2201

REACTIVE POWER ALARM

0 to 2

1

F115

0

2202

ASSIGN ALARM RELAYS (2-5)

1 to 4

1

F50

16

2203

POSITIVE Mvar ALARM LEVEL

3

2 to 201

1

x rated

F14

85

2205

NEGATIVE Mvar ALARM LEVEL

3

2 to 201

1

x rated

F14

85

2207

NEGATIVE Mvar ALARM DELAY

2 to 1200

1

s

F2

10

2208

REACTIVE POWER ALARM EVENTS

0 to 1

1

F105

0

2209

REACTIVE POWER TRIP

0 to 2

1

F115

0

220A

ASSIGN TRIP RELAYS (1-4)

0 to 3

1

F50

1

220B

POSITIVE Mvar TRIP LEVEL

3

2 to 201

1

Mvar

F14

80

220D

NEGATIVE Mvar TRIP LEVEL

3

2 to 201

1

Mvar

F14

80

220F

NEGATIVE Mvar TRIP DELAY

2 to 1200

1

s

F2

10

2210

POSITIVE Mvar TRIP DELAY

2 to 1200

1

s

F2

200

2211

POSITIVE Mvar ALARM DELAY

2 to 1200

1

s

F2

100

POWER ELEMENTS / REVERSE POWER

2240

BLOCK REVERSE POWER FROM ONLINE

0 to 5000

1

s

F1

1

2241

REVERSE POWER ALARM

0 to 2

1

F115

0

2242

ASSIGN ALARM RELAYS (2-5)

1 to 4

1

F50

16

2243

REVERSE POWER ALARM LEVEL

2 to 99

1

× Rated

F14

5

2245

REVERSE POWER ALARM DELAY

2 to 1200

1

s

F2

100

2246

REVERSE POWER ALARM EVENTS

0 to 1

1

F105

0

2247

REVERSE POWER TRIP

0 to 2

1

F115

0

2248

ASSIGN TRIP RELAYS (1-4)

0 to 3

1

F50

1

2249

REVERSE POWER TRIP LEVEL

2 to 99

1

× Rated

F14

5

224B

REVERSE POWER TRIP DELAY

2 to 1200

1

s

F2

200

Table 6–1: 489 MEMORY MAP (SHEET 15 OF 24)

ADDR NAME

RANGE

STEP

UNITS

FORMAT

DEFAULT

1, 2, 3

See Table footnotes on page 6–33