6 open rtd sensor, 7 rtd short/low temperature, Open rtd sensor -54 – GE 489 User Manual

Page 104: Rtd short/low temperature -54

Advertising
background image

4-54

489 Generator Management Relay

GE Multilin

4.9 S8 RTD TEMPERATURE

4 SETPOINTS

4

4.9.6 OPEN RTD SENSOR

SETPOINTS

ÖØ

S8 RTD TEMPERATURE

ÖØ

OPEN RTD SENSOR

The 489 has an Open RTD Sensor Alarm. This alarm will look at all RTDs that have either an alarm or trip programmed and
determine if an RTD connection has been broken. Any RTDs that do not have a trip or alarm associated with them will be
ignored for this feature. When a broken sensor is detected, the assigned output relay will operate and a message will
appear on the display identifying the RTD that is broken. It is recommended that if this feature is used, the alarm be pro-
grammed as latched so that intermittent RTDs are detected and corrective action may be taken.

4.9.7 RTD SHORT/LOW TEMPERATURE

PATH: SETPOINTS

ÖØ

S8 RTD TEMPERATURE

ÖØ

RTD SHORT/LOW TEMP

The 489 has an RTD Short/Low Temperature alarm. This alarm will look at all RTDs that have either an alarm or trip pro-
grammed and determine if an RTD has either a short or a very low temperature (less than –50°C). Any RTDs that do not
have a trip or alarm associated with them will be ignored for this feature. When a short/low temperature is detected, the
assigned output relay will operate and a message will appear on the display identifying the RTD that caused the alarm. It is
recommended that if this feature is used, the alarm be programmed as latched so that intermittent RTDs are detected and
corrective action may be taken.

„ OPEN RTD SENSOR
„ [ENTER] for more

OPEN RTD SENSOR:

Off

Range: Off, Latched, Unlatched

ASSIGN ALARM

RELAYS (2-5): ---5

Range: Any combination of Relays 2 to 5

OPEN RTD SENSOR

ALARM EVENTS: Off

Range: On, Off

„ RTD SHORT/LOW TEMP
„ [ENTER] for more

RTD SHORT/LOW TEMP

ALARM: Off

Range: Off, Latched, Unlatched

ASSIGN ALARM

RELAYS (2-5): ---5

Range: Any combination of Relays 2 to 5

RTD SHORT/LOW TEMP

ALARM EVENTS: Off

Range: On, Off

ENTER