489 Generator Management Relay

GE Multilin

6.3 MODBUS MEMORY MAP

6 COMMUNICATIONS

6

489 SETUP / SERIAL PORTS

1010

SLAVE ADDRESS

1 to 254

1

F1

254

1011

COMPUTER RS485 BAUD RATE

0 to 5

1

F101

4

1012

COMPUTER RS485 PARITY

0 to 2

1

F102

0

1013

AUXILIARY RS485 BAUD RATE

0 to 5

1

F101

4

1014

AUXILIARY RS485 PARITY

0 to 2

1

F102

0

1015

PORT USED FOR DNP

0 to 3

1

F216

0

1016

DNP SLAVE ADDRESS

0 to 255

1

F1

255

1017

DNP TURNAROUND TIME

0 to 100

10

ms

F1

10

489 SETUP / REAL TIME CLOCK

1030

DATE

N/A

N/A

N/A

F18

N/A

1032

TIME

N/A

N/A

N/A

F19

N/A

1034

IRIG-B TYPE

0 to 2

1

F220

0

489 SETUP / MESSAGE SCRATCHPAD

1060

Scratchpad

0 to 40

1

F22

_

1080

Scratchpad

0 to 40

1

F22

_

10A0

Scratchpad

0 to 40

1

F22

_

10C0

Scratchpad

0 to 40

1

F22

_

10E0

Scratchpad

0 to 40

1

F22

_

489 SETUP / CLEAR DATA

1130

CLEAR LAST TRIP DATA

0 to 1

1

F103

0

1131

CLEAR MWh and Mvarh METERS

0 to 1

1

F103

0

1132

CLEAR PEAK DEMAND DATA

0 to 1

1

F103

0

1133

CLEAR RTD MAXIMUMS

0 to 1

1

F103

0

1134

CLEAR ANALOG I/P MIN/MAX

0 to 1

1

F103

0

1135

CLEAR TRIP COUNTERS

0 to 1

1

F103

0

1136

CLEAR EVENT RECORD

0 to 1

1

F103

0

1137

CLEAR GENERATOR INFORMATION

0 to 1

1

F103

0

1138

CLEAR BREAKER INFORMATION

0 to 1

1

F103

0

SYSTEM SETUP / CURRENT SENSING

1180

PHASE CT PRIMARY

10 to 50001

1

Amps

F1

50001

1181

GROUND CT

0 to 3

1

F104

0

1182

GROUND CT RATIO

10 to 10000

1

: 1 / :5

F1

100

SYSTEM SETUP / VOLTAGE SENSING

11A0

VT CONNECTION TYPE

0 to 2

1

F106

0

11A1

VOLTAGE TRANSFORMER RATIO

100 to 30000

1

: 1

F3

500

11A2

NEUTRAL V.T. RATIO

100 to 24000

1

: 1

F3

500

11A3

NEUTRAL VOLTAGE TRANSFORMER

0 to 1

1

F103

0

SYSTEM SETUP / GEN. PARAMETERS

11C0

GENERATOR RATED MVA

50 to 2000001

1

MVA

F13

2000001

11C2

GENERATOR RATED POWER FACTOR

5 to 100

1

F3

100

11C3

GENERATOR VOLTAGE PHASE-PHASE

100 to 30001

1

V

F1

30001

11C4

GENERATOR NOMINAL FREQUENCY

0 to 3

1

Hz

F107

0

11C5

GENERATOR PHASE SEQUENCE

0 to 2

1

F124

0

SYSTEM SETUP / SERIAL START/STOP

11E0

SERIAL START/STOP INITIATION

0 to 1

1

F105

0

11E1

STARTUP INITIATION RELAYS (2-5)

1 to 4

1

F50

0

11E2

SHUTDOWN INITIATION RELAYS (1-4)

0 to 3

1

F50

0

11E3

SERIAL START/STOP EVENTS

0 to 1

1

F105

0

DIGITAL INPUTS / BREAKER STATUS

1200

BREAKER STATUS

0 to 1

1

F209

1

DIGITAL INPUTS / GENERAL INPUT A

1210

ASSIGN DIGITAL INPUT

0 to 7

1

F210

0

1211

ASSERTED DIGITAL INPUT STATE

0 to 1

1

F131

0

1212

INPUT NAME

0 to 12

1

F22

_

1218

BLOCK INPUT FROM ONLINE

0 to 5000

1

s

F1

0

1219

GENERAL INPUT A CONTROL

0 to 1

1

F105

0

121A

PULSED CONTROL RELAY DWELL TIME

0 to 250

1

s

F2

0

121B

ASSIGN CONTROL RELAYS (1-5)

0 to 4

1

F50

0

121C

GENERAL INPUT A CONTROL EVENTS

0 to 1

1

F105

0

121D

GENERAL INPUT A ALARM

0 to 2

1

F115

0

121E

ASSIGN ALARM RELAYS (2-5)

1 to 4

1

F50

16

121F

GENERAL INPUT A ALARM DELAY

1 to 50000

1

s

F2

50

1220

GENERAL INPUT A ALARM EVENTS

0 to 1

1

F105

0

1221

GENERAL INPUT A TRIP

0 to 2

1

F115

0

1222

ASSIGN TRIP RELAYS (1-4)

0 to 3

1

F50

1

Table 6–1: 489 MEMORY MAP (SHEET 7 OF 24)

ADDR NAME

RANGE

STEP

UNITS

FORMAT

DEFAULT

1, 2, 3

See Table footnotes on page 6–33