S7 power elements, 1 power measurement conventions, 8 s7 power elements – GE 489 User Manual

Page 95: Power measurement conventions -45

Advertising
background image

GE Multilin

489 Generator Management Relay

4-45

4 SETPOINTS

4.8 S7 POWER ELEMENTS

4

4.8S7 POWER ELEMENTS

4.8.1 POWER MEASUREMENT CONVENTIONS

Generation of power will be displayed on the 489 as positive watts. By convention, an induction generator normally requires
reactive power from the system for excitation. This is displayed on the 489 as negative vars. A synchronous generator on
the other hand has its own source of excitation and can be operated with either lagging or leading power factor. This is dis-
played on the 489 as positive vars and negative vars, respectively. All power quantities are measured from the phase-
phase voltage and the currents measured at the output CTs.

Figure 4–9: POWER MEASUREMENT CONVENTIONS