7 clear data, Clear data -11 – GE 489 User Manual

Page 61

Advertising
background image

GE Multilin

489 Generator Management Relay

4-11

4 SETPOINTS

4.2 S1 489 SETUP

4

4.2.7 CLEAR DATA

PATH: SETPOINTS

Ö

S1 489 SETUP

ÖØ

CLEAR DATA

These commands may be used to clear various historical data.

CLEAR LAST TRIP DATA: The Last Trip Data may be cleared by executing this command.

CLEAR MWh and Mvarh METERS: Executing this command will clear the MWh and Mvarh metering to zero.

CLEAR PEAK DEMAND DATA: Execute this command to clear peak demand values.

CLEAR RTD MAXIMUMS: All maximum RTD temperature measurements are stored and updated each time a new
maximum temperature is established. Execute this command to clear the maximum values.

CLEAR ANALOG I/P MIN/MAX: The minimum and maximum analog input values are stored for each Analog Input.
Those minimum and maximum values may be cleared at any time.

CLEAR TRIP COUNTERS: There are counters for each possible type of trip. Those counters may be cleared by exe-
cuting this command.

CLEAR EVENT RECORD: The event recorder saves the last 40 events, automatically overwriting the oldest event. If
desired, all events can be cleared using this command to prevent confusion with old information.

CLEAR GENERATOR INFORMATION: The number of thermal resets and the total generator running hours can be
viewed in actual values. On a new installation, or if new equipment is installed, this information is cleared through this
setpoint.

CLEAR BREAKER INFORMATION: The total number of breaker operations can be viewed in actual values. On a new
installation or if maintenance work is done on the breaker, this accumulator can be cleared with this setpoint.

„ CLEAR DATA
„ [ENTER] for more

CLEAR LAST TRIP

DATA: No

Range: No, Yes

RESET MWh and Mvarh

METERS: No

Range: No, Yes

CLEAR PEAK DEMAND

DATA: No

Range: No, Yes

CLEAR RTD

MAXIMUMS: No

Range: No, Yes

CLEAR ANALOG I/P

MIN/MAX: No

Range: No, Yes

CLEAR TRIP

COUNTERS: No

Range: No, Yes

CLEAR EVENT

RECORD: No

Range: No, Yes

CLEAR GENERATOR

INFORMATION: No

Range: No, Yes

CLEAR BREAKER

INFORMATION: No

Range: No, Yes

ENTER

ESCAPE

р

р

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

Advertising