GE Multilin

489 Generator Management Relay

1-5

1 INTRODUCTION

1.2 SPECIFICATIONS

1

RS485 Baud Rates:

300, 1200, 2400, 4800, 9600, 19200

RS232 Baud Rate:

9600

Parity:

None, Odd, Even

Protocol:

Modbus

®

RTU / half duplex, DNP 3.0

ANALOG CURRENT OUTPUT

Type:

Active

Range:

4 to 20mA, 0 to 1 mA
(must be specified with order)

Accuracy:

±1% of full scale

4 to 20 mA max. load:

1.2 k

Ω

0 to 1mA max. load:

10 k

Ω

Isolation:

36 Vpk
(isolated with RTDs and analog inputs)

4 Assignable Outputs:

Phase A, B, C output current
3 phase average current
negative sequence current
generator load
hottest stator RTD
hottest bearing RTD
RTD # 1 to 12
AB voltage
BC voltage
CA voltage
average phase-phase voltage
volts/hertz
frequency
3rd harmonic neutral voltage
power factor
3 phase reactive power (Mvar)
3 phase real power (MW)
3 phase apparent power (MVA)
analog inputs 1 to 4
tachometer
thermal capacity used
I, Mvar, MW, MVA demands
Torque

OUTPUT RELAYS

Relay contacts must be considered unsafe to touch
when the 489 is energized! If the output relay con-
tacts are required for low voltage accessible applica-
tions, it is the customer's responsibility to ensure
proper insulation levels.

Configuration:

6 electromechanical Form C relays

Contact Material:

silver alloy

Operate Time:

10 ms

Max Ratings for 100000 operations:

TERMINALS

Low Voltage (A, B, C, D terminals): 12 AWG max
High Voltage (E, F, G, H terminals): #8 ring lug,

10 AWG wire standard

POWER METERING

Range:

0.000 to 2000.000 ±Mw, ±Mvar, MVA

Accuracy

at Iavg

< 2 × CT:

±1% of

Ч 2 Ч CT × VT × VT full-scale

at Iavg

> 2 × CT:

±1.5% of

Ч 20 Ч CT × VT × VT full-scl.

WATTHOUR AND VARHOUR METERING

Description:

Continuous total of +watthours and
±varhours

Range:

0.000 to 4000000.000 MvarHours

Timing Accuracy:

±0.5%

Update Rate:

50 ms

DEMAND METERING

Metered Values:

Maximum Phase Current
3 Phase Real Power
3 Phase Apparent Power
3 Phase Reactive Power

Measurement Type:

Rolling Demand

Demand Interval:

5 to 90 minutes in steps of 1

Update Rate:

1 minute

Elements:

Alarm

GENERAL INPUT A TO G (DIGITAL INPUT)

Configurable:

Assignable Digital Inputs 1 to 7

Time Delay:

0.1 to 5000.0 s in steps of 0.1

Block From Online:

0 to 5000 s in steps of 1

Timing Accuracy:

±100 ms or ±0.5% of total time

Elements:

Trip, Alarm, and Control

SEQUENTIAL TRIP (DIGITAL INPUT)

Configurable:

Assignable to Digital Inputs 1 to 7

Pickup Level:

0.02 to 0.99

× rated MW in steps of 0.01

Low Forward Power / Reverse Power

Time Delay:

0.2 to 120.0 s in steps of 0.1

Pickup Accuracy:

see power metering

Timing Accuracy:

±100 ms or ±0.5% of total time

Elements:

Trip

FIELD BREAKER DISCREPANCY (DIGITAL INPUT)

Configurable:

Assignable to Digital Inputs 1 to 7

Time Delay:

0.1 to 500.0 s in steps of 0.1

Timing Accuracy:

±100 ms or ±0.5% of total time

Elements:

Trip

TACHOMETER (DIGITAL INPUT)

Configurable:

Assignable to Digital Inputs 4 to 7

RPM Measurement:

100 to 7200 RPM

Duty Cycle of Pulse:

>10%

Pickup Level:

101 to 175

× rated speed in steps of 1

Time Delay:

1 to 250 s in steps of 1

VOLTAGE

MAKE/CARRY

BREAK

MAX.

LOAD

CTS

0.2 s

DC

RESISTIVE

30 V

10 A

30 A

10 A

300 W

125 V

10 A

30 A

0.5 A

62.5 W

250 V

10 A

30 A

0.3 A

75 W

DC

INDUCTIVE

L/R = 40 ms

30 V

10 A

30 A

5 A

150 W

125 V

10 A

30 A

0.25 A

31.3 W

250 V

10 A

30 A

0.15 A

37.5 W

AC

RESISTIVE

120 V

10 A

30 A

10 A

2770 VA

250 V

10 A

30 A

10 A

2770 VA

WARNING

AC

INDUCTIVE

PF = 0.4

120 V

10 A

30 A

4 A

480 VA

250 V

10 A

30 A

3 A

750 VA

VOLTAGE

MAKE/CARRY

BREAK

MAX.

LOAD

CTS

0.2 s

3

3