489 Generator Management Relay

GE Multilin

5.5 A4 MAINTENANCE

5 ACTUAL VALUES

5

5.5.2 GENERAL COUNTERS

PATH: ACTUAL VALUES

ÖØ

A4 MAINTENANCE

ÖØ

GENERAL COUNTERS

One of the 489 general counters will count the number of breaker operations over time. This may be useful information for
breaker maintenance. The number of breaker operations is incremented whenever the breaker status changes from closed
to open and all phase currents are zero. Another counter counts the number of thermal resets if one of the assignable digi-
tal inputs is assigned to thermal reset. This may be useful information when troubleshooting. When either of these counters
reaches 50000, that counter will reset to 0. Each counter can also be cleared using the

S1 489 SETUP

ÖØ

CLEAR DATA

ÖØ

CLEAR BREAKER INFORMATION

setpoint. The number of breaker operations will not update if a digital input programmed as

Test Input is shorted.

5.5.3 TIMERS

PATH: ACTUAL VALUES

ÖØ

A4 MAINTENANCE

ÖØ

TIMERS

The 489 accumulates the total online time for the generator. This may be useful for scheduling routine maintenance. When
this timer reaches 1000000, it resets to 0. This timer can be cleared using the

S1 489 SETUP

ÖØ

CLEAR DATA

ÖØ

CLEAR

GENERATOR INFORMATION

setpoint. The generator hours online will not update if a digital input programmed as Test Input is

shorted.

„ GENERAL COUNTERS
„ [ENTER] for more

NUMBER OF BREAKER

OPERATIONS: 0

Range: 0 to 50000

NUMBER OF THERMAL

RESETS: 0

Range: 0 to 50000. Seen only if a digital input is

assigned to Thermal Reset.

„ TIMERS
„ [ENTER] for more

GENERATOR HOURS

ONLINE: 0

h

Range: 1 to 1000000 hrs.