489 Generator Management Relay

6-29

6 COMMUNICATIONS

6.3 MODBUS MEMORY MAP

6

MONITORING / RUNNING HOUR SETUP

2AC0

INITIAL GEN. RUNNING HOUR

0 to 999999

1

h

F12

0

2AC2

GEN. RUNNING HOUR ALARM

0 to 2

1

F115

0

2AC3

ASSIGN ALARM RELAYS (2-5)

1 to 4

1

F50

16

2AC4

GEN. RUNNING HOUR LIMIT

1 to 1000000

1

h

F12

1000

2AC6

RESERVED

ANALOG I/O / ANALOG OUTPUT 1

2B00

ANALOG OUTPUT 1

0 to 42

1

F127

0

ANALOG I/O / ANALOG OUTPUT 2

2B01

ANALOG OUTPUT 2

0 to 42

1

F127

0

ANALOG I/O / ANALOG OUTPUT 3

2B02

ANALOG OUTPUT 3

0 to 42

1

F127

0

ANALOG I/O / ANALOG OUTPUT 4

2B03

ANALOG OUTPUT 4

0 to 42

1

F127

0

ANALOG I/O / ANALOG OUTPUTS

2B04

IA OUTPUT CURRENT MIN

0 to 2000

1

× FLA

F3

0

2B05

IA OUTPUT CURRENT MAX

0 to 2000

1

× FLA

F3

125

2B06

IB OUTPUT CURRENT MIN

0 to 2000

1

× FLA

F3

0

2B07

IB OUTPUT CURRENT MAX

0 to 2000

1

× FLA

F3

125

2B08

IC OUTPUT CURRENT MIN

0 to 2000

1

× FLA

F3

0

2B09

IC OUTPUT CURRENT MAX

0 to 2000

1

× FLA

F3

125

2B0A

AVG OUTPUT CURRENT MIN

0 to 2000

1

× FLA

F3

0

2B0B

AVG OUTPUT CURRENT MAX

0 to 2000

1

× FLA

F3

125

2B0C

NEG. SEQ. CURRENT MIN

0 to 2000

1

%FLA

F1

0

2B0D

NEG. SEQ. CURRENT MAX

0 to 2000

1

%FLA

F1

100

2B0E

AVERAGED GEN. LOAD MIN

0 to 2000

1

× FLA

F3

0

2B0F

AVERAGED GEN. LOAD MAX

0 to 2000

1

× FLA

F3

125

2B10

HOTTEST STATOR RTD MIN

–50 to 250

1

°C

F4

0

2B11

HOTTEST STATOR RTD MAX

–50 to 250

1

°C

F4

200

2B12

HOTTEST BEARING RTD MIN

–50 to 250

1

°C

F4

0

2B13

HOTTEST BEARING RTD MAX

–50 to 250

1

°C

F4

200

2B14

AMBIENT RTD MIN

–50 to 250

1

°C

F4

0

2B15

AMBIENT RTD MAX

–50 to 250

1

°C

F4

70

2B16

RTD #1 MIN

–50 to 250

1

°C

F4

0

2B17

RTD #1 MAX

–50 to 250

1

°C

F4

200

2B18

RTD #2 MIN

–50 to 250

1

°C

F4

0

2B19

RTD #2 MAX

–50 to 250

1

°C

F4

200

2B1A

RTD #3 MIN

–50 to 250

1

°C

F4

0

2B1B

RTD #3 MAX

–50 to 250

1

°C

F4

200

2B1C

RTD #4 MIN

–50 to 250

1

°C

F4

0

2B1D

RTD #4 MAX

–50 to 250

1

°C

F4

200

2B1E

RTD #5 MIN

–50 to 250

1

°C

F4

0

2B1F

RTD #5 MAX

–50 to 250

1

°C

F4

200

2B20

RTD #6 MIN

–50 to 250

1

°C

F4

0

2B21

RTD #6 MAX

–50 to 250

1

°C

F4

200

2B22

RTD #7 MIN

–50 to 250

1

°C

F4

0

2B23

RTD #7 MAX

–50 to 250

1

°C

F4

200

2B24

RTD #8 MIN

–50 to 250

1

°C

F4

0

2B25

RTD #8 MAX

–50 to 250

1

°C

F4

200

2B26

RTD #9 MIN

–50 to 250

1

°C

F4

0

2B27

RTD #9 MAX

–50 to 250

1

°C

F4

200

2B28

RTD #10 MIN

–50 to 250

1

°C

F4

0

2B29

RTD #10 MAX

–50 to 250

1

°C

F4

200

2B2A

RTD #11 MIN

–50 to 250

1

°C

F4

0

2B2B

RTD #11 MAX

–50 to 250

1

°C

F4

200

2B2C

RTD #12 MIN

–50 to 250

1

°C

F4

0

2B2D

RTD #12 MAX

–50 to 250

1

°C

F4

200

2B2E

AB VOLTAGE MIN

0 to 150

1

× Rated

F3

0

2B2F

AB VOLTAGE MAX

0 to 150

1

× Rated

F3

125

2B30

BC VOLTAGE MIN

0 to 150

1

× Rated

F3

0

2B31

BC VOLTAGE MAX

0 to 150

1

× Rated

F3

125

2B32

CA VOLTAGE MIN

0 to 150

1

× Rated

F3

0

2B33

CA VOLTAGE MAX

0 to 150

1

× Rated

F3

125

2B34

AVERAGE VOLTAGE MIN

0 to 150

1

× Rated

F3

0

2B35

AVERAGE VOLTAGE MAX

0 to 150

1

× Rated

F3

125

2B36

VOLTS/HERTZ MIN

0 to 200

1

× Rated

F3

0

Table 6–1: 489 MEMORY MAP (SHEET 20 OF 24)

ADDR NAME

RANGE

STEP

UNITS

FORMAT

DEFAULT

1, 2, 3

See Table footnotes on page 6–33