489 voltage dependent overload protection curves – GE 489 User Manual

Page 113

Advertising
background image

GE Multilin

489 Generator Management Relay

4-63

4 SETPOINTS

4.10 S9 THERMAL MODEL

4

The 489 takes the information provided and create protection curves for any voltage between the minimum and 100%. For
values above the voltage in question, the 489 extrapolates the safe stall protection curve to 110% voltage. This current
level is calculated by taking the locked rotor current at 100% voltage and multiplying by 1.10. For trip times above the 110%
current level, the trip time of 110% will be used (see the figure below).

Figure 4–15: VOLTAGE DEPENDENT OVERLOAD PROTECTION CURVES

The safe stall curve is in reality a series of safe stall points for different voltages. For a given voltage, there can be
only one value of stall current, and therefore only one safe stall time.

489

VOLTAGE DEPENDENT

OVERLOAD PROTECTION CURVES

808831A3.CDR

1

1

2

3

4

5

6

7

8

2

3

4

5

6

7

8

9

10

20

30

40

50

60

70

80

90

100

T

IM

E

TO

T

R

IP

(S

E

C

O

N

D

S

)

MULTIPLES OF FULL LOAD AMPS

200

300

400

500

600

700

800

900

1000

Acceleration Intersect at 80%V

Custom Curve

Acceleration Intersect at 100%V

Safe Stall Time at 80%V,

80%V Stall Current

Safe Stall Time at 100%V,

100%V Stall Current

Safe Stall Points

Extrapolated to 110%V

GE Multilin

NOTE

Advertising