GE 489 User Manual

Page 180

Advertising
background image

6-18

489 Generator Management Relay

GE Multilin

6.3 MODBUS MEMORY MAP

6 COMMUNICATIONS

6

DIGITAL INPUTS / GENERAL INPUT F

12B0

ASSIGN DIGITAL INPUT

0 to 7

1

F210

0

12B1

ASSERTED DIGITAL INPUT STATE

0 to 1

1

F131

0

12B2

INPUT NAME

0 to 12

1

F22

_

12B8

BLOCK INPUT FROM ONLINE

0 to 5000

1

s

F1

0

12B9

GENERAL INPUT F CONTROL

0 to 1

1

F105

0

12BA

PULSED CONTROL RELAY DWELL TIME

0 to 250

1

s

F2

0

12BB

ASSIGN CONTROL RELAYS (1-5)

0 to 4

1

F50

0

12BC

GENERAL INPUT F CONTROL EVENTS

0 to 1

1

F105

0

12BD

GENERAL INPUT F ALARM

0 to 2

1

F115

0

12BE

ASSIGN ALARM RELAYS (2-5)

1 to 4

1

F50

16

12BF

GENERAL INPUT F ALARM DELAY

1 to 50000

1

s

F2

50

12C0

GENERAL INPUT F ALARM EVENTS

0 to 1

1

F105

0

12C1

GENERAL INPUT F TRIP

0 to 2

1

F115

0

12C2

ASSIGN TRIP RELAYS (1-4)

0 to 3

1

F50

1

12C3

GENERAL INPUT F TRIP DELAY

1 to 50000

1

s

F2

50

DIGITAL INPUTS / GENERAL INPUT G

12D0

ASSIGN DIGITAL INPUT

0 to 7

1

F210

0

12D1

ASSERTED DIGITAL INPUT STATE

0 to 1

1

F131

0

12D2

INPUT NAME

0 to 12

1

F22

_

12D8

BLOCK INPUT FROM ONLINE

0 to 5000

1

s

F1

0

12D9

GENERAL INPUT G CONTROL

0 to 1

1

F105

0

12DA

PULSED CONTROL RELAY DWELL TIME

0 to 250

1

s

F2

0

12DB

ASSIGN CONTROL RELAYS (1-5)

0 to 4

1

F50

0

12DC

GENERAL INPUT G CONTROL EVENTS

0 to 1

1

F105

0

12DD

GENERAL INPUT G ALARM

0 to 2

1

F115

0

12DE

ASSIGN ALARM RELAYS (2-5)

1 to 4

1

F50

16

12DF

GENERAL INPUT G ALARM DELAY

1 to 50000

1

s

F2

50

12E0

GENERAL INPUT G ALARM EVENTS

0 to 1

1

F105

0

12E1

GENERAL INPUT G TRIP

0 to 2

1

F115

0

12E2

ASSIGN TRIP RELAYS (1-4)

0 to 3

1

F50

1

12E3

GENERAL INPUT G TRIP DELAY

1 to 50000

1

s

F2

50

DIGITAL INPUTS / REMOTE RESET

1300

ASSIGN DIGITAL INPUT

0 to 7

1

F210

0

DIGITAL INPUTS / TEST INPUT

1310

ASSIGN DIGITAL INPUT

0 to 7

1

F210

0

DIGITAL INPUTS / THERMAL RESET

1320

ASSIGN DIGITAL INPUT

0 to 7

1

F210

0

DIGITAL INPUTS / DUAL SETPOINTS

1340

ASSIGN DIGITAL INPUT

0 to 7

1

F210

0

1341

ACTIVE SETPOINT GROUP

0 to 1

1

F118

0

1342

EDIT SETPOINT GROUP

0 to 1

1

F118

0

DIGITAL INPUTS / SEQUENTIAL TRIP

1360

ASSIGN DIGITAL INPUT

0 to 7

1

F210

0

1361

SEQUENTIAL TRIP TYPE

0 to 1

1

F206

0

1362

ASSIGN TRIP RELAYS (1-4)

0 to 3

1

F50

1

1363

SEQUENTIAL TRIP LEVEL

2 to 99

1

× Rated MW

F14

5

1365

SEQUENTIAL TRIP DELAY

2 to 1200

1

s

F2

10

DIGITAL INPUTS / FIELD-BKR DISCREP.

1380

ASSIGN DIGITAL INPUT

0 to 7

1

F210

0

1381

FIELD STATUS CONTACT

0 to 1

1

F109

0

1382

ASSIGN TRIP RELAYS (1-4)

0 to 3

1

F50

1

1383

FIELD-BKR DISCREP. TRIP DELAY

1 to 5000

1

s

F2

10

DIGITAL INPUTS / TACHOMETER

13A0

ASSIGN DIGITAL INPUT

0 to 7

1

F210

0

13A1

RATED SPEED

100 to 3600

1

RPM

F1

3600

13A2

TACHOMETER ALARM

0 to 2

1

F115

0

13A3

ASSIGN ALARM RELAYS (2-5)

1 to 4

1

F50

16

13A4

TACHOMETER ALARM SPEED

101 to 175

1

%Rated

F1

110

13A5

TACHOMETER ALARM DELAY

1 to 250

1

s

F1

1

13A6

TACHOMETER ALARM EVENTS

0 to 1

1

F105

0

13A7

TACHOMETER TRIP

0 to 2

1

F115

0

13A8

ASSIGN TRIP RELAYS (1-4)

0 to 3

1

F50

1

13A9

TACHOMETER TRIP SPEED

101 to 175

1

%Rated

F1

110

13AA

TACHOMETER TRIP DELAY

1 to 250

1

s

F1

1

Table 6–1: 489 MEMORY MAP (SHEET 9 OF 24)

ADDR NAME

RANGE

STEP

UNITS

FORMAT

DEFAULT

1, 2, 3

See Table footnotes on page 6–33

Advertising