2 analog inputs 1 to 4, 2 analog inputs 1 to 4 -76, Table 4–8: analog output parameter – GE 489 User Manual

Page 126

Advertising
background image

4-76

489 Generator Management Relay

GE Multilin

4.12 S11 ANALOG I/O

4 SETPOINTS

4

4.12.2 ANALOG INPUTS 1 TO 4

PATH: SETPOINTS

ÖØ

S11 ANALOG I/O

ÖØ

ANALOG INPUT 1(4)

Table 4–8: ANALOG OUTPUT PARAMETER SELECTION

PARAMETER NAME

RANGE / UNITS

STEP

DEFAULT

MIN.

MAX

IA Output Current

0.00 to 20.00

× FLA

0.01

0.00

1.25

IB Output Current

0.00 to 20.00

× FLA

0.01

0.00

1.25

IC Output Current

0.00 to 20.00

× FLA

0.01

0.00

1.25

Avg. Output Current

0.00 to 20.00

× FLA

0.01

0.00

1.25

Neg. Seq. Current

0 to 2000% FLA

1

0

100

Averaged Gen. Load

0.00 to 20.00

× FLA

0.01

0.00

1.25

Hottest Stator RTD

–50 to +250°C or –58 to +482°F

1

0

200

Hottest Bearing RTD

–50 to +250°C or –58 to +482°F

1

0

200

Ambient RTD

–50 to +250°C or –58 to +482°F

1

–50

60

RTDs 1 to 12

–50 to +250°C or –58 to +482°F

1

–50

250

AB Voltage

0.00 to 1.50

× Rated

0.01

0.00

1.25

BC Voltage

0.00 to 1.50

× Rated

0.01

0.00

1.25

CA Voltage

0.00 to 1.50

× Rated

0.01

0.00

1.25

Volts/Hertz

0.00 to 2.00

× Rated

0.01

0.00

1.50

Frequency

0.00 to 90.00 Hz

0.01

59.00

61.00

Neutral Volt. (3rd)

0 to 25000 V

0.1

0.0

45.0

Average Voltage

0.00 to 1.50

× Rated

0.01

0.00

1.25

Power Factor

0.01 to 1.00 lead/lag

0.01

0.8 lag

0.8 lead

Reactive Power (Mvar)

–2.00 to 2.00

× Rated

0.01

0.00

1.25

Real Power

–2.00 to 2.00

× Rated

0.01

0.00

1.25

Apparent Power

0.00 to 2.00

× Rated

0.01

0.00

1.25

Analog Inputs 1 to 4

–50000 to +50000

1

0

50000

Tachometer

0 to 7200 RPM

1

3500

3700

Thermal Capacity Used

0 to 100%

1

0

100

Current Demand

0.00 to 20.00

× FLA

0.01

0.00

1.25

Mvar Demand

0.00 to 2.00

× Rated

0.01

0.00

1.25

MW Demand

0.00 to 2.00

× Rated

0.01

0.00

1.25

MVA Demand

0.00 to 2.00

× Rated

0.01

0.00

1.25

„ ANALOG INPUT 1
„ [ENTER] for more

ANALOG INPUT1:

Disabled

Range: Disabled, 4-20 mA, 0-20 mA, 0-1 mA

ANALOG INPUT1 NAME:

Analog I/P 1

Range: 12 alphanumeric characters

ANALOG INPUT1 UNITS:

Units

Range: 6 alphanumeric characters

ANALOG INPUT1

MINIMUM: 0

Range: –50000 to 50000 in steps of 1

ANALOG INPUT1

MAXIMUM: 100

Range: –50000 to 50000 in steps of 1

BLOCK ANALOG INPUT1

FROM ONLINE: 0 s

Range: 0 to 5000 sec. in steps of 1

ENTER

ESCAPE

р

р

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE