2 overcurrent alarm, 3 offline overcurrent, Overcurrent alarm -24 – GE 489 User Manual

Page 74: Offline overcurrent -24

Advertising
background image

4-24

489 Generator Management Relay

GE Multilin

4.6 S5 CURRENT ELEMENTS

4 SETPOINTS

4

4.6.2 OVERCURRENT ALARM

PATH: SETPOINTS

ÖØ

S5 CURRENT ELEMENTS

Ö

OVERCURRENT ALARM

If enabled as Latched or Unlatched, the Overcurrent Alarm will function as follows: If the average generator current (RMS)
measured at the output CTs exceeds the level programmed for the period of time specified, an alarm will occur. If pro-
grammed as unlatched, the alarm will reset itself when the overcurrent condition is no longer present. If programmed as
latched, once the overcurrent condition is gone, the reset key must be pressed to reset the alarm. The generator FLA is cal-
culated as:

(EQ 4.8)

4.6.3 OFFLINE OVERCURRENT

PATH: SETPOINTS

ÖØ

S5 CURRENT ELEMENTS

ÖØ

OFFLINE O/C

When a synchronous generator is offline, there should be no measurable current flow in any of the three phases unless the
unit is supplying its own station load. Also, since the generator is not yet online, differentiation between system faults and
machine faults is easier. The offline overcurrent feature is active only when the generator is offline and uses the neutral end
CT measurements (Ia, Ib, Ic). It may be set much more sensitive than the differential element to detect high impedance
phase faults. Since the breaker auxiliary contacts wired to the 489 Breaker Status input may not operate at exactly the
same time as the main breaker contacts, the time delay should be coordinated with the difference of the operation times. In
the event of a low impedance fault, the differential element will still shutdown the generator quickly.

If the unit auxiliary transformer is on the generator side of the breaker, the pickup level must be set greater
than the unit auxiliary load.

„ OVERCURRENT ALARM
„ [ENTER] for more

OVERCURRENT

ALARM: Off

Range: Off, Latched, Unlatched

ASSIGN ALARM

RELAYS (2-5): ---5

Range: Any combination of Relays 2 to 5

OVERCURRENT ALARM

LEVEL: 1.01 x FLA

Range: 0.10 to 1.50

× FLA in steps of 0.01

OVERCURRENT ALARM

DELAY: 0.1 s

Range: 0.1 to 250.0 s in steps of 0.1

OVERCURRENT ALARM

EVENTS: Off

Range: On, Off

„ OFFLINE O/C
„ [ENTER] for more

OFFLINE OVERCURRENT

TRIP: Off

Range: Off, Latched, Unlatched

ASSIGN TRIP

RELAYS (1-4): 1---

Range: Any combination of Relays 1 to 4

OFFLINE OVERCURRENT

PICKUP: 0.05 x CT

Range: 0.05 to 1.00

× CT in steps of 0.01

OFFLINE OVERCURRENT

TRIP DELAY: 5 cycles

Range: 3 to 99 cycles in steps of 1

ENTER

ESCAPE

р

р

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

Generator FLA

3 rated generator phase-phase voltage

×

=

ENTER

ESCAPE

р

р

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

NOTE

Advertising