GE Multilin

489 Generator Management Relay

4-19

4 SETPOINTS

4.4 S3 DIGITAL INPUTS

4

One of assignable digital inputs 4 to 7 may be assigned to the tachometer function to measure mechanical speed. The time
between each input closure is measured and converted to an RPM value based on one closure per revolution. If an over-
speed trip or alarm is enabled, and the measured RPM exceeds the threshold setpoint for the time specified by the delay, a
trip or alarm will occur. The RPM value can be viewed with the

A2 METERING DATA

ÖØ

SPEED

ÖØ

TACHOMETER

actual

value.

For example, an inductive proximity probe or hall effect gear tooth sensor may be used to sense the key on the generator.
The probe could be powered from the +24V from the digital input power supply. The NPN transistor output could be taken
to one of the assignable digital inputs assigned to the tachometer function.

4.4.11 WAVEFORM CAPTURE

PATH: SETPOINTS

ÖØ

S3 DIGITAL INPUTS

ÖØ

WAVEFORM CAPTURE

This feature may be used to trigger the waveform capture from an external contact. When one of the inputs is assigned to
the Waveform Capture function, shorting that input will trigger the waveform.

4.4.12 GROUND SWITCH STATUS

PATH: SETPOINTS

ÖØ

S3 DIGITAL INPUTS

ÖØ

GND SWITCH STATUS

This function is used to detect the status of a grounding switch for the generator for which the relay is installed. Refer to
Appendix B for Application Notes.

„ WAVEFORM CAPTURE
„ [ENTER] for more

ASSIGN DIGITAL

INPUT: None

Range: None, Input 1 to Input 7. If an input is assigned to

the Tachometer, it may not be used here.

„ GND SWITCH STATUS
„ [ENTER] for more

ASSIGN DIGITAL

INPUT: None

Range: None, Input 1 to Input 7. If an input is assigned to

the Tachometer, it may not be used here.

GROUND SWITCH

CONTACT: Auxiliary a

Range: Auxiliary a, Auxiliary b

ENTER

ESCAPE

р

р

ENTER

ESCAPE

р

р

MESSAGE

ESCAPE