GE Multilin

489 Generator Management Relay

4-53

4 SETPOINTS

4.9 S8 RTD TEMPERATURE

4

4.9.5 RTD 12

PATH: SETPOINTS

ÖØ

S8 RTD TEMPERATURE

ÖØ

RTD #12

RTDs 12 defaults to Ambient RTD type. The Ambient selection allows the RTD to be used to monitor ambient temperature.
There are individual alarm and trip configurations for this RTD. Trip voting has been added for extra reliability in the event of
RTD malfunction. If enabled, a second RTD must also exceed the trip temperature of the RTD being checked before a trip
will be issued. If the RTD is chosen to vote with itself, the voting feature is disabled. The RTD name may be changed if
desired.

„ RTD #12
„ [ENTER] for more

RTD #12 APPLICATION:

Ambient

Range: Stator, Bearing, Ambient, Other, None

RTD #12 NAME:

Range: 8 alphanumeric characters

RTD #12 ALARM:

Off

Range: Off, Latched, Unlatched

ASSIGN ALARM

RELAYS (2-5): ---5

Range: Any combination of Relays 2 to 5.

RTD #12 ALARM

TEMPERATURE: 60°C

Range: 1 to 250°C in steps of 1

RTD #12 ALARM

EVENTS: Off

Range: On, Off

RTD #12 TRIP:

Off

Range: Off, Latched, Unlatched

RTD #12 TRIP VOTING:

RTD #12

Range: RTD #1 to RTD #12

ASSIGN TRIP

RELAYS (1-4): 1---

Range: Any combination of Relays 1 to 4

RTD #12 TRIP

TEMPERATURE: 80°C

Range: 1 to 250°C in steps of 1

ENTER

ESCAPE

р

р

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE