2 pre-fault setup, 2 pre-fault setup -79 – GE 489 User Manual

Page 129

Advertising
background image

GE Multilin

489 Generator Management Relay

4-79

4 SETPOINTS

4.13 S12 TESTING

4

4.13.2 PRE-FAULT SETUP

PATH: SETPOINTS

ÖØ

S12 TESTING

ÖØ

PRE-FAULT SETUP

The values entered under Pre-Fault Values will be substituted for the measured values in the 489 when the

SIMULATION

MODE

is "Simulate Pre-Fault".

„ PRE-FAULT SETUP
„ [ENTER] for more

PRE-FAULT Iphase

OUTPUT: 0.00 x CT

Range: 0.00 to 20.00

× CT in steps of 0.01

PRE-FAULT VOLTAGES

PHASE-N: 1.00 x Rated

Range: 0.00 to 1.50

× Rated in steps of 0.01

Entered as a phase-to-neutral quantity.

PRE-FAULT CURRENT

LAGS VOLTAGE: 0°

Range: 0 to 359° in steps of 1

PRE-FAULT Iphase

NEUTRAL: 0.00 x CT

Range: 0.00 to 20.00

× CT in steps of 0.01

180° phase shift with respect to Iphase OUTPUT

PRE-FAULT CURRENT

GROUND: 0.00 x CT

Range: 0.00 to 20.00

× CT in steps of 0.01

CT is either XXX:1 or 50:0.025

PRE-FAULT VOLTAGE

NEUTRAL: 0 Vsec

Range

0.0 to 100.0 Vsec in steps of 0.1
Fundamental value only in secondary units

PRE-FAULT STATOR

RTD TEMP: 40°C

Range: –50 to 250°C in steps of 1

PRE-FAULT BEARING

RTD TEMP: 40°C

Range: –50 to 250°C in steps of 1

PRE-FAULT OTHER

RTD TEMP: 40°C

Range: –50 to 250°C in steps of 1

PRE-FAULT AMBIENT

RTD TEMP: 40°C

Range: –50 to 250°C in steps of 1

PRE-FAULT SYSTEM

FREQUENCY: 60.0 Hz

Range: 5.0 to 90.0 Hz in steps of 0.1

PRE-FAULT ANALOG

INPUT 1: 0%

Range: 0 to 100% in steps of 1

PRE-FAULT ANALOG

INPUT 2: 0%

Range: 0 to 100% in steps of 1

PRE-FAULT ANALOG

INPUT 3: 0%

Range: 0 to 100% in steps of 1

PRE-FAULT ANALOG

INPUT 4: 0%

Range: 0 to 100% in steps of 1

ENTER

ESCAPE

р

р

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

Advertising