A2 metering data, 1 current metering, 3 a2 metering data – GE 489 User Manual

Page 145: Current metering -13

Advertising
background image

GE Multilin

489 Generator Management Relay

5-13

5 ACTUAL VALUES

5.3 A2 METERING DATA

5

5.3A2 METERING DATA

5.3.1 CURRENT METERING

PATH: ACTUAL VALUES

ÖØ

A2 METERING DATA

Ö

CURRENT METERING

All measured current values are displayed here.

A, B, C AMPS

represent the output side CT measurements:

A, B, C NEUT.

AMPS

the neutral end CT measurements, and

A, B, C DIFF. AMPS

the differential operating current calculated as the vector

difference between the output side and the neutral end CT measurements on a per phase basis. The 489 negative-
sequence current is defined as the ratio of negative-sequence current to generator rated FLA, I

2

/ FLA

× 100%. The gener-

ator full load amps is calculated as: generator rated MVA / (

× generator phase-phase voltage). Polar coordinates for

measured currents are also shown using Va (wye connection) or Vab (open delta connection) as a zero angle reference
vector. In the absence of a voltage signal (Va or Vab), the IA output current is used as the zero angle reference vector.

„ CURRENT METERING
„ [ENTER] for more

A:

0

B:

0

C:

0

Amps

Range: 0 to 999999 A

a:

0

b:

0

c:

0

Neut. Amps

Range: 0 to 999999 A

a:

0

b:

0

c:

0

Diff. Amps

Range: 0 to 999999 A

AVERAGE PHASE

CURRENT: 0 Amps

Range: 0 to 999999 A

GENERATOR LOAD:

0% FLA

Range: 0 to 2000% FLA

NEGATIVE SEQUENCE

CURRENT: 0% FLA

Range: 0 to 2000% FLA

PHASE A CURRENT:

0 A

0° Lag

Range: 0 to 999999 A, 0 to 359°

PHASE B CURRENT:

0 A

0° Lag

Range: 0 to 999999 A, 0 to 359°

PHASE C CURRENT:

0 A

0° Lag

Range: 0 to 999999 A, 0 to 359°

NEUT. END A CURRENT:

0 A

0° Lag

Range: 0 to 999999 A, 0 to 359°

NEUT. END B CURRENT:

0 A

0° Lag

Range: 0 to 999999 A, 0 to 359°

NEUT. END C CURRENT:

0 A

0° Lag

Range: 0 to 999999 A, 0 to 359°

DIFF. A CURRENT:

0 A

0° Lag

Range: 0 to 999999 A, 0 to 359°

DIFF. B CURRENT:

0 A

0° Lag

Range: 0 to 999999 A, 0 to 359°

DIFF. C CURRENT:

0 A

0° Lag

Range: 0 to 999999 A, 0 to 359°

GROUND CURRENT:

0.0 A

0° Lag

Range: 0.0 to 200000.0 A, 0 to 359°

Seen only if 1 A Ground CT input is used

GROUND CURRENT:

0.00 A

0° Lag

Range: 0.00 to 100.00 A, 0 to 359°

Seen only if 50:0.025 Ground CT is used

ENTER

ESCAPE

р

р

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

3

Advertising