4.10 S9 THERMAL MODEL

4 SETPOINTS

4

To illustrate the Voltage Dependent Overload Curve feature, the thermal limits shown in Figure 4–13: Thermal Limits for
High Inertial Load on page 4–61 wil
l be used.

1.

Construct a custom curve for the running overload thermal limit. If the curve does not extend to the acceleration ther-
mal limits, extend it such that the curve intersects the acceleration thermal limit curves. (see CUSTOM CURVE below).

2.

Enter the per unit current value for the acceleration overload curve intersect with the custom curve for 80% voltage.
Also enter the per unit current and safe stall protection time for 80% voltage (see ACCELERATION CURVE below).

3.

Enter the per unit current value for the acceleration overload curve intersect with the custom curve for 100% voltage.
Also enter the per unit current and safe stall protection time for 100% voltage (see ACCELERATION CURVE below)

Figure 4–14: VOLTAGE DEPENDENT OVERLOAD CURVES

489

VOLTAGE DEPENDENT OVERLOAD

(CUSTOM CURVE)

808827A3.CDR

1

1

2

3

4

5

6

7

8

2

3

4

5

6

7

8

9

10

20

30

40

50

60

70

80

90

100

T

IM

E

TO

T

R

IP

(S

E

C

O

N

D

S

)

MULTIPLES OF FULL LOAD AMPS

200

300

400

500

600

700

800

900

1000

Acceleration Intersect at 80%V

Acceleration Intersect at 100%V

GE Multilin

489

VOLTAGE DEPENDENT OVERLOAD

(ACCELERATION CURVES)

808828A3.CDR

1

1

2

3

4

5

6

7

8

2

3

4

5

6

7

8

9

10

20

30

40

50

60

70

80

90

100

T

IM

E

TO

T

R

IP

(S

E

C

O

N

D

S

)

MULTIPLES OF FULL LOAD AMPS

200

300

400

500

600

700

800

900

1000

489 Custom Curve

GE Multilin

Advertising