GE Multilin

489 Generator Management Relay

5-11

5 ACTUAL VALUES

5.2 A1 STATUS

5

The alarm pickup messages may be very useful during testing. They will indicate if a alarm feature has been enabled, if it is
inactive (not picked up), timing out (picked up and timing), active alarm (still picked up, timed out, and causing an alarm), or
latched alarm (no longer picked up, but had timed out and caused a alarm that is latched). These values may also be par-
ticularly useful as data transmitted to a master device for monitoring.

OPEN SENSOR

PICKUP: Not Enabled

Range: Not Enabled, Inactive, Timing Out, Active Alarm,

Latched Alarm.

SHORT/LOW TEMP

PICKUP: Not Enabled

Range: Not Enabled, Inactive, Timing Out, Active Alarm,

Latched Alarm.

THERMAL MODEL

PICKUP: Not Enabled

Range: Not Enabled, Inactive, Timing Out, Active Alarm,

Latched Alarm.

TRIP COUNTER

PICKUP: Not Enabled

Range: Not Enabled, Inactive, Timing Out, Active Alarm,

Latched Alarm.

BREAKER FAILURE

PICKUP: Not Enabled

Range: Not Enabled, Inactive, Timing Out, Active Alarm,

Latched Alarm.

TRIP COIL MONITOR

PICKUP: Not Enabled

Range: Not Enabled, Inactive, Timing Out, Active Alarm,

Latched Alarm.

VT FUSE FAILURE

PICKUP: Not Enabled

Range: Not Enabled, Inactive, Timing Out, Active Alarm,

Latched Alarm.

CURRENT DEMAND

PICKUP: Not Enabled

Range: Not Enabled, Inactive, Timing Out, Active Alarm,

Latched Alarm.

MW DEMAND

PICKUP: Not Enabled

Range: Not Enabled, Inactive, Timing Out, Active Alarm,

Latched Alarm.

Mvar DEMAND

PICKUP: Not Enabled

Range: Not Enabled, Inactive, Timing Out, Active Alarm,

Latched Alarm.

MVA DEMAND

PICKUP: Not Enabled

Range: Not Enabled, Inactive, Timing Out, Active Alarm,

Latched Alarm.

ANALOG I/P 1

PICKUP: Not Enabled

Range: Not Enabled, Inactive, Timing Out, Active Alarm,

Latched Alarm. Reflects programmed Analog
Input Name. Seen only if input is enabled.

ANALOG I/P 2

PICKUP: Not Enabled

Range: see ANALOG I/P 1 PICKUP

ANALOG I/P 3

PICKUP: Not Enabled

Range: see ANALOG I/P 1 PICKUP

ANALOG I/P 4

PICKUP: Not Enabled

Range: see ANALOG I/P 1 PICKUP

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

Advertising